Product Main

Specifications

 
It is used as connection cable of inspection devices and instruments with high demand on interference resistant performance in computer network and control system.
Executive standard:
Q/TK.J.04.030-2004 or BS5308 standard for reference
Performance for Usage:
1. AC rated voltage U0/U: 300/500V. Long term working temperature of cable conductor is 70℃ & 105℃ for cable with PVC insulation, 70℃ for cable with PE insulation and 90℃ for cable with XLPE insulation.(XLPE insulation includes silane XLPE & irradiation XLPE insulation.)
2. Min. environment temperature is -40℃ for fixed laying and -15℃ for non-fixed laying. Environment temperature shall be no less than 0℃ for installing.
3. Min. bending radius allowed by cable is no less than 6 times that of cable OD for non-armored soft cable or braided shielding cable and 12 times that of cable OD for cable with metallic tape wrapped shielding or steel wire/steel tape armor.
Type, Description and Definition
Example: DJYP3VP3-32
32: Steel wire winding armor PVC outer sheath
P3: Aluminum-plastic compound tape wrapped general shielding 
V: PVC inner sheath
P3: Aluminum-plastic compound tape wrapped individual shielding
Y: PE insulation
DJ: Series number of computer cable
Main Technical Parameter
  1. DC Resistance of Conductor at 20℃
Nominal cross section area (mm2)
Pieces of conductor/diameter of single piece
DC resistance of conductor at 20℃
A
B
C
A, B
R
0.5
1/0.80
7/0.30
16/0.20
≤36.0
≤39.0
0.75
1/0.97
7/0.37
24/0.20
≤24.5
≤26.0
1.0
1/1.13
7/0.43
32/0.20
≤18.1
≤19.5
1.5
1/1.38
7/0.52
30/0.25
≤12.1
≤13.3
2.5
1/1.78
7/0.68
49/0.25
≤7.41
≤7.98
2. Insulation Resistance at 20℃

Performance item
PVC insulation
PE, XLPE insulation
Insulation resistance at 20℃
≥25
≥500
3. Cable shall endure A.C. voltage test of 2000V under power frequency for 1min without puncture of insulation. And testing temperature is environment temperature.