Detailed Product Description
1.Water-cooled Diesel Engine
2.Open Type Diesel Genset
3.Cummins OEM Service
4.AMF controller
5.copy stamford generator
2.Open Type Diesel Genset
3.Cummins OEM Service
4.AMF controller
5.copy stamford generator
The main parameters of the set
|
||
The model of the unit:
|
400GF
|
|
Power:
|
400KW(500KVA)
|
|
Rated voltage:
|
220V
|
|
Rated frequency:
|
60Hz
|
|
The factor of rated power
|
COS=0.8lagging
|
|
The regulating rate of steady voltage:
|
≤1%
|
|
The regulating rate of instantaneous voltage:
|
-15%~ +20%
|
|
The time of steady voltage:
|
≤1.5sec
|
|
The waving rate of voltage:
|
≤1.0%
|
|
The regulating rate of steady frequency:
|
≤3%
|
|
The regulating rate of instantaneous frequency:
|
≤±10%
|
|
The time of steady frequency:
|
3sec
|
|
The waving rate of frequency:
|
≤1%
|
|
Displacement (L):
|
38
|
|
The waste of fuel with full load:
|
≤207g/kwh
|
|
Lube-oil consumption (L):
|
135
|
|
Dimension
(L×W×H)mm:
|
Open Type
|
3300×1150×1700
|
With Packing( plywood case)
|
3400×1250×1850
|
|
Weight(KG):
|
Open Type
|
4000
|
With Packing( plywood case)
|
5000
|
|
The main parameters of the diesel engine
|
||
Brand:
|
CUMMINS
|
|
Model:
|
KTA19-G3
|
|
Type:
|
Four strokes, waste gas turbine boost, direct spurting type
|
|
Cylinder:
|
6 cylinders
|
|
Cooling way:
|
Water cooling
|
|
Rotating speed:
|
1800r/min
|
|
The regulation of rotating speed:
|
Electric speed regulator
|
|
Starting way:
|
DC24V\ starting with electricity
|
|
The main parameters of the generator
|
||
Brand:
|
Kaijieli
|
|
Model :
|
TWGII354B
|
|
Type:
|
Brushless ,Self-excite, AVR automatic voltage regulating
|
|
The connecting way of the phase:
|
Three phases four lines
|
|
Insulation degree:
|
H degree
|
|
Enclosure degree:
|
IP22
|