Product Main

Specifications

PD319-2 Series Multifunction Harmonic Analyzer is designed for measuring electic parameters, harmonics, multi-rates energy, power quality, S.O.E event reording and communication. They are applied in electric energy management power monitoring and controls, power substation automation, smart building and switchgears, etc.
  PD319-2 Series Multifunction Harmonic Analyzer is designed according to (DL/T614-1997, GB/T17883-1999, GB/T17882-1999, DL/T645-1997, GB/T15284-2002, GB/T14549-1993) .
 
     
 
 Technical Data
 
Accuracy Current, voltage 0.2 class, Frequency 0.1Hz, Power, Active electric energy 0.5class, Reactive electric energy 2 class
Display LCD Display
Input
measurement
Network Three Phase Four Line, Three Phase Three Line
Rated value Voltage AC100V, AC400V, Current AC1A, AC5A
Overloading Continuance: 1.2 times, Instantaneous: Voltage 2 time(10s) Current 10 times(5s)
Power consumption Voltage<0.6VA(each phase), Current<0.4VA(each phase)
Impedance Voltage circuit>300kΩ
 
input measurement Frequency 50Hz±10%
Harmonics Voltage, Current(2~31 time) harmonic
Mnlti-rate electric energy 3 rates, 8 time bands
Clock/Calendar Clock error 0.5s/day
Oiwer syooky Working range AC, DC 80V~270V
Power consumption ≤5VA
Output Digital Interface RS-485 interface, MODBUS-RTU protocol
Pulse output 2 loops power pulse output, Photo-coupler relay, Constant: 3200imp/kWh(kvarh)
Switch value output 2 loops light coupler
lnstallation Installation mode Panel mounting
Cutout size 92x92mm
Outline dimension 96x96x100mm
Operation condition Ambient temp: -10~55℃, Relative humidity≤93%, No corrosion air, Height (above sea level)≤2500m
Isolation withstand voltage Input and power supply>2kV, Input and output>2kV
Insulating resistance ≥100MΩ