PD319-2 Series Multifunction Harmonic Analyzer is designed for measuring electic parameters, harmonics, multi-rates energy, power quality, S.O.E event reording and communication. They are applied in electric energy management power monitoring and controls, power substation automation, smart building and switchgears, etc.
PD319-2 Series Multifunction Harmonic Analyzer is designed according to (DL/T614-1997, GB/T17883-1999, GB/T17882-1999, DL/T645-1997, GB/T15284-2002, GB/T14549-1993) . |
|
|
|
|
Technical Data |
|
|
|
Accuracy |
Current, voltage 0.2 class, Frequency 0.1Hz, Power, Active electric energy 0.5class, Reactive electric energy 2 class |
|
Display |
LCD Display |
Input
measurement |
Network |
Three Phase Four Line, Three Phase Three Line |
|
Rated value |
Voltage AC100V, AC400V, Current AC1A, AC5A |
|
Overloading |
Continuance: 1.2 times, Instantaneous: Voltage 2 time(10s) Current 10 times(5s) |
|
Power consumption |
Voltage<0.6VA(each phase), Current<0.4VA(each phase) |
|
Impedance |
Voltage circuit>300kΩ |
|
|
input measurement |
Frequency |
50Hz±10% |
|
Harmonics |
Voltage, Current(2~31 time) harmonic |
|
Mnlti-rate electric energy |
3 rates, 8 time bands |
|
Clock/Calendar |
Clock error 0.5s/day |
|
Oiwer syooky |
Working range |
AC, DC 80V~270V |
|
Power consumption |
≤5VA |
|
Output |
Digital Interface |
RS-485 interface, MODBUS-RTU protocol |
|
Pulse output |
2 loops power pulse output, Photo-coupler relay, Constant: 3200imp/kWh(kvarh) |
|
Switch value output |
2 loops light coupler |
|
lnstallation |
Installation mode |
Panel mounting |
|
Cutout size |
92x92mm |
|
Outline dimension |
96x96x100mm |
|
Operation condition |
Ambient temp: -10~55℃, Relative humidity≤93%, No corrosion air, Height (above sea level)≤2500m |
|
Isolation withstand voltage |
Input and power supply>2kV, Input and output>2kV |
|
Insulating resistance |
≥100MΩ |
|