PD319 series motor protectors are inplicated to AC 380V and AC 660V low voltage system,as new intelligent integrated device that protect and monitor low-volt asynchronous motor and increased-safety motor.Besides function of motor protecting,they can provide information that the device running and tripping,so avoid of errors caused by overloading,stop slewing,breaking phase,the three phase unbalance,creepage.They are used to eletrical power,landification,light industry,coal,paper industry,steel industry,textile industry,and so on..
Standards:GB3836.3-2000 GB14048.4-2003 IE255-5,
IEC255-22
PD319 series motor protectors are inplicated to AC
 
 
 Technical Data
Rated Voltage:AC380V,AC660V
Rated Current:0.5-800V
Rated Working Frequency:50Hz
Working Temperature:-20~60 centigrade
Storing Temperature:-25~70 centigrade
Relative Humidity:less than 90%
Attitude:not higher than 2500 meters
Air Condition:no medium that can cause explosion,no corrosive metal and electric dust.
Installed in place no strong striked and storm
Relay output
Tripping relay J1
1 nomal open and closed transfer contact
Programmable relay J1
1 nomal open contact(such as alarm setting)
Output capacity
250VAC 5A 24VDC 5A
Auxiliary source
AC source voltage
AC 220V  AC380V±15%
DC source voltage
DC24V  DC110V±15%
Frequency
50Hz±2%
Consumption
Normal work≤3W  Protector starting≤5W
Zero-sequence current input
Zero-sequence transformer LJ1
Hole size Φ45
Zero-sequence transformer LJ2
Hole size Φ80
 
Electric Test
Insulating Resistance
Standard
IEC255-5  100MΩ/500V
Insulating Test
Standard
IEC255-5
Medium strength test
2kV(r.m.s.),50Hz,1min
Attact voltage test
5kV(peak),1MHz,400times/s,keep on 2S
EMC antijam
Standard
IEC200-22
Common-mode interference
2.5kV(peak)
Defferential mode interferance
1.0kV(peak),100kHz;50times/s,keep on 2s
Radiation field interference frequency
27MHz~1000Hz;density of field:10V/m
Static discharge interference
8kV
Fast transient interference
2kV;5kHz;bipolar;keep on 1min
 
 
Current
Current rating(In)
Set current (le) range
Remarks
2A
0.5~2A
One time current across three phase current transformer of the protector
5A
1~5A
25A
5~25A
100A
25~100A
200/5A
80~200A
Additional 5 transformers across three phase current transformers in the protector 5 circles by two times
300/5A
120~300A
400/5A
160~400A
500/5A
200~500A
600/5A
240~600A
800/5A
300~800A
 
Main Function
 
 
 
Three Phase Four Line
Three Phase Three Line
Phase voltage
Ua, Ub, Uc
Line voltage
Uab, Ubc, Uca
Uab, Ucb
Current
Ia, Ib, Ic
Ia,Ic
Active power
Pa, Pb, Pc, P
P
Reactive power
Qa, Qb, Qc, Q
Q
 
Three Phase Four Line
Three Phase Three Line
Apparent power
Sa, Sb, Sc, S
S
Power factor
PFa, PFb, PFC, PF
PF
Voltage harmonics
Ua, Ub, Uc (2~31times)
Uab, Ucb (2~31times)
Current harmonics
Ia, Ib, Ic (2~31times )
Ia, Ic (2~31times)
Voltage unbalance degree
Yv
Current unbalance degree
Yi
Voltage component
Positive sequence Up, Negative sequence Un
Current component
Positive sequence Ip, Negative sequence In
Frequency
F
Active energy
+kWh, -kWh
Reactive energy
+kvarh, -kvarh
Time-sharing calculating
Peak, Shoulder, Vally, Total
SOE event reording
20 pieces SOE event recording
Remote surveillance input
2 loops of switch value input
Remote control output
2 loops of switch value output
Communication interface
1 loop of RS-485 interface, MODBUS-RTU
Pulse output
2 loops of energy pulse output
Referenced application
Electric power system, Transformer, Gen-sets low voltage system wire-in, Energy measurement, Communication and management