230/120V AC,5/25A,50/60Hz(see meter)
Performance:corresponding to EN62052 and “CE” requirements
Accuracy class:1
Mounting:on a DIN-rail corresponding to DIN EN50022
1TE:18min (DIN 43880)
Interface: optical coupler (SO corresponding to DIN 43864)
Impulse valence=Ra=0.5 or 1.0 Wh/imp (see meter)
3 colour LED
Green:Consumption less than 4W or no load
Salmon/pink:Consumption > 4W,flasing rate= consumption
Flashing red:Connection run
Display:6+1 digits=999999,1kWh
Power consumption: < 2VA
Voltage operating range:0.02~25A
Starting current at Cos-Phi=1.typical 15mA
Frequency range:50Hz or 60Hz ± 10%
Registered harmonics:up to 7kHz
Temperature range:-20℃ to + 65℃
Relative air humidity maximum:
average value of year:75%,short time value:95%
 
Installation guide
Vericated version:230/120V ± 10%,max 25A,50/60Hz(see meter)
For monitoring purpose only
For intem measurements:electrical operational/limiting values are valid
Power supply:
-Corresponding with mode of connection 1000 of DIN 43856 (see meter)
-Phase supply lead “L” to terminal 1
-Neutral supply lead “N” to terminal 4
-Phase consumption lead “L” to terminal 3
-Neutral consumption lead ”N” to terminal 6
-Fuses & wiring
-For fuse 10A,tripping characteristic B,minimum wire thickness 1,5mm2
- For fuse 16A,tripping characteristic B,minimum wire thickness 2,5mm2
Passive impulse contact:
-corresponding to “SO” conditions of DIN 43864:
18-27V:max 27mA:max length of lead:20m
Impulse length >30ms,connection to terminal SO+ & SO-
-Limits of values:max 60VDC: max 30mA
Diode against wrong connection is integrated (parallel)