Product Main

Specifications

  • Working conditions 
     
1.Altitude : no more than 1000m; 
2.Ambient temperature: -5 Degree Centigrade to 45 Degree Centigrade; 
3.Relative humidity of air: no more than 90%(at 25 Degree Centigrade);
4.The site of usage: indoor;  
5. Applied for AC HV. Test  or breakdown test to XLPE cable , disconnector and surge arrester, the test voltage is no more than 400KV, the test current is no more than 1A 
  • Composition of set  
1. CQSB(J) -400kVA/400kV/3kV PD-free AC test transformer            1
2. 400KV intelligence controller                                                               1
3. DT-200kVA/380V/0~3.3KV electric regulator                                     1
4. TRF -400kV capacitive voltage divider                                                1
5. BHR -1/ 5kohm power frequency protective resistor                       1
6. 300kVA/3kV compensation reactor                                                     1 
  • General technical parameters 
1. Rated capacity: 400kVA; 
2. Working power: 0.38kV; 
3. Working frequency:  50HZ; 
4. Rated output voltage: 400kV;
5. Rated output current: 1A;
6. Running time: 60 minutes on, 60 m off, 8 times/day 
7. Temperature raise: under rated running condition, temperature raise of all parts are no more than 65K;
8. Measurement accuracy: effective value of system measurement is1.5 grade;
9.PD level from the system itself: no more than 5PC at rated voltage(400KV) 
  • Technical  functions 
1. Input voltage: 380V for control;  3KV for transformer
2. It can monitor voltage and current at HV side, and current and voltage at LV side 
3. Protective function: zero, over current and over voltage protection 
4. Measurement  meters : 1.0 grade;
5.)Functions are as folowing:.
  • Withstand time to automatical step-down function 
  •  Withstand time adopts digital-display timer. When it reaches withstand time, system will step-down automatically 
  • Zero switch on and zero step-up function: There is zero–limit function. If regulator is not at zero, HV output button can’t switch on, in order to ensure step-up is from zero. Regulaotor.
  • Over current function: There is electric over current relay, anti- interference is strong, operation is fast, which avoid damage from over current. 
  • Over voltage protection function: There is electric over voltage protective board, it is fast and reliable; over voltage protection setting is regulated by manually, displayed by digital. It is intuitive, convinient and accurate.. 
  • Real-time monitor function for all test date: It can monitor voltage and voltage at HV side, and current and voltage at LV side 
  • Automatic test aided computer intelligence system..
  • Manual testing on software in computer. 
  • Automatic test with each setting value for Voltage and time ; 
  • Saving function for each Test setting .
  • Test Report printing 
  • Computer Hardware should be use the latest Industrial model. 
  • Display monitor should be 19” or above size..

remark: wuhan fanke company can produce so many models according test objects condition and test usage.