| model Specifications and parameters | C2K | ||||||
| Rated power | 2000VA/1600W | ||||||
| AC Input | Input system | Single phrase & earth ground | |||||
| Ranged voltage | 208/220/230/240Vac | ||||||
| Frequency | 50/60Hz | ||||||
| Voltage range | 115~300VAC±5 | ||||||
| Frequency range | 50/60±5Hz | ||||||
| Voltage range of bypass | 80VAC×(1±5%)285VAC×(1±5%) | ||||||
| Battery | Voltage range of battery | 72VDC | |||||
| Input | |||||||
| Battery capacity*Quantity | 12VDC*6 | ||||||
| Backup Time (half/full loaded) | Half loaded≥10minutes, Full loaded ≥5minutes(standard) | ||||||
| Transient rush current in boot-up state | <150% of rated current | ||||||
| Battery charger time | Charger to 90% battery capacity in 5 hours(standard) | ||||||
| Dependent on the capacity of external batteries(long backup time) | |||||||
| AC | Output system | Single phrase&earth ground | |||||
| Output | |||||||
| Output voltage | 220/110Vac±3%(inverter output) | ||||||
| Output frequency | 50/60±5Hz(normal) 50/60Hz±1%(abnormal) | ||||||
| Dynamic voltage transient range | <5% | ||||||
| Dynamic transient restore | < 60ms | ||||||
| Waveform | Sine WaveTHD<3%(linear load) Sine WaveTHD<8%(nonlinear load) | ||||||
| Input powerfactor | 0.8 | ||||||
| Overload capability | 105125%≥ 60s, 126150%≥30s The recover point is 90% | ||||||
| Input current peak coefficient | 31 | ||||||
| Transfer time | < 0ms | ||||||
| Panel indicator system | LCD indicator, show the status | ||||||
| of UPS and operation parameter | |||||||
| Communications | RS232(turn to 485), stem node | ||||||
| Alarm Function | AC/DC input under abnormal , overload condition | ||||||
| and inverter problems | |||||||
| Protection Function | AC input or output above or below the range of voltage | ||||||
| Overload , over | |||||||
| temperature and short circuit protection | |||||||
| Conduction | Satisfy YD/T983-1998A | ||||||
| Radiation | Satisfy YD/T983-1998A | ||||||
| Noise Immunity | Satisfy YD/T983-1998A | ||||||
| Insulating resistance | > 2MΩ500VDC | ||||||
| Insulating strength | 2121VDC(AC input, output to ground, DC input to AC output), | ||||||
| without flashover in one minute) | |||||||
| Cooling system | wind cooling | ||||||
| Frequency | <55dB(1M) | ||||||
| Working | Temperature | 10~ +40 | |||||
| enviroment | |||||||
| humidity | 0~95%, no condensation | ||||||
| Altitude | ≤1500m, satisfy GB3859.2-93 | ||||||
| Storage | Inverter temperature | -40~+65 | |||||
| envirement | |||||||
| humidity | 0~95%, no condensation | ||||||
| Dimensions(mm)(W*H*D) | 190×445×336 | ||||||