Typical Description of AC/Partial Discharge Test System for High Voltage cables
This test system is mainly used to AC test and PD detection for XLPE cables 10-500KV and other apparatus.
A typical series resonant test system designed for HV/PD test e. g. for Power Cable testing is shown as below.

Technical Parameters of AC/Partial Discharge Test System for High Voltage cables
 
 
Item
Rated voltage of
XLPE cable
 
 
6/10,8.7/10KV,
    XLPE
 
21/35,26/35KV
XLPE(2.5Uo)
 
21/35,26/35KV
XLPE(3.5Uo)
 
63.5/110KV,
  XLPE
 
76.2/132KV,
  XLPE
 
127/220KV,
  XLPE
Rated output voltage﹠capacity
 
35kv,350KVA
 
75kv,750KVA
 
120kv,1200KVA
 
200kv,2000KVA
 
250kv,2500KVA
 
350kv,5000KVA
Input voltage﹠capacity
50Hz,380V,
20KVA
50Hz,380V,
40KVA
50Hz,380V,
60KVA
50Hz,380V,
100KVA
50Hz,380V,
175KVA
50Hz,380V,
250KVA
PD noise level pC
Under 100% rated output voltage,<2pC
Measuring precision of voltage 
±1%
Locating accuracy of PD faults
Up to 1% of the cable length and can be reached ≤±1m
Environmental temperature
10℃~40℃
Relative humidity/altitude/
indoor or outdoor
 
≤95% /≤1000m altitude/indoor use
Grounding for the test system
One or two copper rod,the depth grounding resistance shall be less than 1Ω
The insulation isolated resistance between the test area and surrounding
 
>1000MΩ measuring when water immerssion
Design quality factorQ
20
 
Power supply for the test system
 
10kv/0.4kv
20kvA Single transformer
 
10kv/0.4kv
40kvA Single transformer
 
10kv/0.4kv
60kvA Single transformer
 
10kv/0.4kv
100kvA Single transformer
10kv,175kvA Single Transformer
Supply from city grid
10kv,250kvA Single Transformer
Supply from city grid
 
 
 
HV reactor
 
35kv/350kvA
Taps:35kv,20kv
Turning range:
35kv0.001-0.9μv
20kv0.021-2.7μv
 
75kv/750kvA
Taps:75kv,40kv
Turning range:
75kv0.021-0.42μv
40kv0.039-1.5μv
 
120kv/1200kvA
Taps:120kv,70kv
Turning range:
120kv0.012-0.27μv70kv0.022-1.0μv
200kv/2000kvA
Taps:200,100,40kv
Turning range:
200kv 0.012-0.20μv
100kv 0.014-0.67μv
40kv0.19-3.9μv
250kv/2500kvA
Taps:250,150,100k
Turning range:
250kv 0.008-0.318μv
150kv 0.024-0.49μv
100kv0.055-1.1μv
350kv/5000kvA
Taps:350,250,150k
Turning range:
350kv 0.022-0.45μv
250kv 0.012-0.25μv
150kv0.035-0.7μv
 
Excit transformer
 
20kvA 1.75/1.0kv
 
35kvA 3.5/2.0kv
 
60kvA 6/3.5kv
 
100kvA 10/5/2kv
 
175kv12.5/7.5/5kv
250kvA
35/17.5/8.75kv
 
Double-shielded isolated transformer
 
380v/380v,20kvA
~10dB
 
380v/380v,35kvA
~10dB
 
380v/380v,60kvA
~10dB
380v/380v,100kvA
(10v/380v100kvA)
~10dB
380v/380v,175kvA
(10v/380v175kvA)
~10dB
 
10v/380v,250kvA
    ~10dB
 
Regulater
380v/0~380v
  20kvA
380v/0~380v
  35kvA
380v/0~380v
  60kvA
380v/0~380v
  100kvA
380v/0~380v
  175kvA
380v/0~380v
  250kvA
HV Divider
35kv ±1%,<2pC
75kv ±1%,<2pC
120kv±1%,<2pC
200kv±1%,<2pC
250kv±1%,<2pC
350kv±1%,<2pC
LV Filter
380v,50A ~20dB
380v,90A ~20dB
380v,160A ~20dB
380v,263A ~20dB
380v,460A ~20dB
380v,657A ~20dB
 
HV Filter
35kv,18A,<2pC,
  >40dB
75kv18.75A<2pC
  >40dB
120kv,20A,<2pC,
  >40dB
200kv,20A,<2pC,
  >40dB
250kv,35A,<2pC,
  >40dB
350kv,33A,<2pC,
  >40dB
Calibration injected capacitor
100pF,35kV,
  <2pC
100pF,75kV,
<2pC
100pF,120kV,
  <2pC
100pF,200kV,
  <2pC
100pF,250kV,
  <2pC
100pF,350kV,
  <2pC
 
Test terminal
Insulation
oil/Freon TE<2pC
Insulation
oil/Freon TE<2pC
Insulation
oil/Freon TE<2pC
Water termination
  CTT 300
Water termination
  CTT 300
Water termination
  CTT 400
PD Detector/Site Locator
JFD series digital PD detector/site Locator
Shielded room(m)
6×4×4.5
6×4×4.5
8×5×4.5
11×7×5
11×7×5
17×10×7
Control room
Inside or outside of shield room
Special devices for locating the PD position closed the cable end
 
Optional
Rail trolley for tested cable drum
Carring capacity:10/15/25/30T,the cable drum can be rotated(optional)