Typical Description of AC/Partial Discharge Test System for High Voltage cables
This test system is mainly used to AC test and PD detection for XLPE cables 10-500KV and other apparatus.
A typical series resonant test system designed for HV/PD test e. g. for Power Cable testing is shown as below.
Technical Parameters of AC/Partial Discharge Test System for High Voltage cables
Technical Parameters of AC/Partial Discharge Test System for High Voltage cables
Item
Rated voltage of
XLPE cable
|
6/10,8.7/10KV,
XLPE
|
21/35,26/35KV
XLPE(2.5Uo)
|
21/35,26/35KV
XLPE(3.5Uo)
|
63.5/110KV,
XLPE
|
76.2/132KV,
XLPE
|
127/220KV,
XLPE
|
|||||
Rated output voltage﹠capacity
|
35kv,350KVA
|
75kv,750KVA
|
120kv,1200KVA
|
200kv,2000KVA
|
250kv,2500KVA
|
350kv,5000KVA
|
|||||
Input voltage﹠capacity
|
50Hz,380V,
20KVA
|
50Hz,380V,
40KVA
|
50Hz,380V,
60KVA
|
50Hz,380V,
100KVA
|
50Hz,380V,
175KVA
|
50Hz,380V,
250KVA
|
|||||
PD noise level pC
|
Under 100% rated output voltage,<2pC
|
||||||||||
Measuring precision of voltage
|
±1%
|
||||||||||
Locating accuracy of PD faults
|
Up to 1% of the cable length and can be reached ≤±1m
|
||||||||||
Environmental temperature
|
10℃~40℃
|
||||||||||
Relative humidity/altitude/
indoor or outdoor
|
≤95% /≤1000m altitude/indoor use
|
||||||||||
Grounding for the test system
|
One or two copper rod,the depth grounding resistance shall be less than 1Ω
|
||||||||||
The insulation isolated resistance between the test area and surrounding
|
>1000MΩ measuring when water immerssion
|
||||||||||
Design quality factorQ
|
20
|
||||||||||
Power supply for the test system
|
10kv/0.4kv
20kvA Single transformer
|
10kv/0.4kv
40kvA Single transformer
|
10kv/0.4kv
60kvA Single transformer
|
10kv/0.4kv
100kvA Single transformer
|
10kv,175kvA Single Transformer
Supply from city grid
|
10kv,250kvA Single Transformer
Supply from city grid
|
|||||
HV reactor
|
35kv/350kvA
Taps:35kv,20kv
Turning range:
35kv0.001-0.9μv
20kv0.021-2.7μv
|
75kv/750kvA
Taps:75kv,40kv
Turning range:
75kv0.021-0.42μv
40kv0.039-1.5μv
|
120kv/1200kvA
Taps:120kv,70kv
Turning range:
120kv0.012-0.27μv70kv0.022-1.0μv
|
200kv/2000kvA
Taps:200,100,40kv
Turning range:
200kv 0.012-0.20μv
100kv 0.014-0.67μv
40kv0.19-3.9μv
|
250kv/2500kvA
Taps:250,150,100k
Turning range:
250kv 0.008-0.318μv
150kv 0.024-0.49μv
100kv0.055-1.1μv
|
350kv/5000kvA
Taps:350,250,150k
Turning range:
350kv 0.022-0.45μv
250kv 0.012-0.25μv
150kv0.035-0.7μv
|
|||||
Excit transformer
|
20kvA 1.75/1.0kv
|
35kvA 3.5/2.0kv
|
60kvA 6/3.5kv
|
100kvA 10/5/2kv
|
175kv12.5/7.5/5kv
|
250kvA
35/17.5/8.75kv
|
|||||
Double-shielded isolated transformer
|
380v/380v,20kvA
~10dB
|
380v/380v,35kvA
~10dB
|
380v/380v,60kvA
~10dB
|
380v/380v,100kvA
(10v/380v100kvA)
~10dB
|
380v/380v,175kvA
(10v/380v175kvA)
~10dB
|
10v/380v,250kvA
~10dB
|
|||||
Regulater
|
380v/0~380v
20kvA
|
380v/0~380v
35kvA
|
380v/0~380v
60kvA
|
380v/0~380v
100kvA
|
380v/0~380v
175kvA
|
380v/0~380v
250kvA
|
|||||
HV Divider
|
35kv ±1%,<2pC
|
75kv ±1%,<2pC
|
120kv±1%,<2pC
|
200kv±1%,<2pC
|
250kv±1%,<2pC
|
350kv±1%,<2pC
|
|||||
LV Filter
|
380v,50A ~20dB
|
380v,90A ~20dB
|
380v,160A ~20dB
|
380v,263A ~20dB
|
380v,460A ~20dB
|
380v,657A ~20dB
|
|||||
HV Filter
|
35kv,18A,<2pC,
>40dB
|
75kv18.75A<2pC
>40dB
|
120kv,20A,<2pC,
>40dB
|
200kv,20A,<2pC,
>40dB
|
250kv,35A,<2pC,
>40dB
|
350kv,33A,<2pC,
>40dB
|
|||||
Calibration injected capacitor
|
100pF,35kV,
<2pC
|
100pF,75kV,
<2pC
|
100pF,120kV,
<2pC
|
100pF,200kV,
<2pC
|
100pF,250kV,
<2pC
|
100pF,350kV,
<2pC
|
|||||
Test terminal
|
Insulation
oil/Freon TE<2pC
|
Insulation
oil/Freon TE<2pC
|
Insulation
oil/Freon TE<2pC
|
Water termination
CTT 300
|
Water termination
CTT 300
|
Water termination
CTT 400
|
|||||
PD Detector/Site Locator
|
JFD series digital PD detector/site Locator
|
||||||||||
Shielded room(m)
|
6×4×4.5
|
6×4×4.5
|
8×5×4.5
|
11×7×5
|
11×7×5
|
17×10×7
|
|||||
Control room
|
Inside or outside of shield room
|
||||||||||
Special devices for locating the PD position closed the cable end
|
Optional
|
||||||||||
Rail trolley for tested cable drum
|
Carring capacity:10/15/25/30T,the cable drum can be rotated(optional)
|