1. General
BD4EA programmable power transmitter specializes in measuring the data of all kinds
of AC networks. It can be connected with the control equipment in measuring and
controlling system. They comply EN 61326:2006 and EN 61010-1:2001.
of AC networks. It can be connected with the control equipment in measuring and
controlling system. They comply EN 61326:2006 and EN 61010-1:2001.
They are a kind of programmable transmitter. The user can program it by front or PC
software. They have many option functions. They can be equipped RS-485 communication Modbus-RTU; or they can output up to 4 analog signals.
software. They have many option functions. They can be equipped RS-485 communication Modbus-RTU; or they can output up to 4 analog signals.
They are a kind of analyzer with excellent cost performance, since they regroup
the functions of traditional electric transmitter and digital meters. Therefore
they are widely being used in kinds of control system, SCADA system and
power management system.
the functions of traditional electric transmitter and digital meters. Therefore
they are widely being used in kinds of control system, SCADA system and
power management system.
2. Technical parameters
|
Technical parameters
|
Value
|
|
|
Input
|
Network
|
Single-phase network; 3-phase balanced network
3-phase unbalanced, 3 wires; 3-phase unbalanced, 4 wires
|
|
Measurable
|
Ia,Ib,Ic,Ua,Ub,Uc,Uab,Ubc,Uca,F,∑P, Pa,Pb,Pc, ∑Q, Qa,Qb,Qc,∑S, Sa,Sb,Sc,∑PF, PFa,PFb,PFc, 4 quadrant energies, multi-rate energies
|
|
|
Frequency
|
45 ~ 65Hz
|
|
|
Voltage
|
AC 100V, 400V (programmable)
|
|
|
Overload: 480V (continuous); 800V during 30s
|
||
|
Consumption: < 0.2VA
|
||
|
Current
|
Rating: AC 1A, 5A (programmable)
|
|
|
Overload: 6A (continuous); 50A during 1s
|
||
|
Consumption: < 0.2VA
|
||
|
Thermal drift
|
<200ppm
|
|
|
Transformation ratio
|
Programmable
|
|
|
Options
|
Analog output
|
Up to 4 outputs, 0 ~ 20mA, 4 ~ 20mA programmable
|
|
Load capacity: ≤500Ω
|
||
|
Communication
|
RS485 (Modbus-RTU protocol)
|
|
|
Pulse
|
2 pulse outputs (open-collector),
|
|
|
Pulse constant: 10000, 40000, 160000 imp/kWh
|
||
|
Precision
|
0.5 (F: 0.05Hz; kVar: 1)
|
|
|
Power supply
|
AC/DC 85 ~ 270V; Consumption ≤ 4VA
|
|
|
Test voltage
|
2kVAC/min (voltage input / power; between current inputs)
|
|
|
1.5kVAC/min (outputs / power)
|
||
|
Insulation
|
input / housing and output / housing >100MΩ
|
|
|
Environment
|
Work T: -10°C ~ +45°C; Storage T: -20°C ~ +70°C
|
|
|
Relative humidity: 5% ~ 95% (no condensation)
|
||
|
Altitude: ≤2500m
|
||