Product Main

Specifications

Measure: three phase I,U,F,P,E,
Output: RS485, Analog, relay output

 
1.  General
PZ Series programmable intelligent three phase current,voltage meter,adopting AC sampling technology,can directly measure current and voltage of three phase grid.It can be used for local display,and connecting industrial control device to form measuring control system.
Meters have RS-485 communication interface,adopt compatible Modbus-RTU protocol can change electric parameter signal into standard analog output or with 1 channel relay alarm output,or with 4 channel(2 channel)switching input/2channel switching output.Based on different request,by pressing related key on instrument panel,parameter setting and control of transformation ratio,alarm,communication etc.can be done.. 
 
2. Specification
PZ48L-AI3
Three Phase Ammeter LCD 
/
PZ96L-AI3
PZ96L-AV3
Three phase Ammeters LCD 
Three phase voltmeters LCD
/C :   RS485 Communication
/J :  Alarm(over current)
/M : 3 analog output(programmable 4-20mA)
/K :  4DI/2DO
 
3.  Technical parameter
Technical
Value
 Input
 Range
voltage: AC100V, 220V, 380V;
current: AC1A, 5A; 
 Overload
voltage: 480V(continuous), 1000V/30s;
current:: 6A (continuous), 50A/1s
 Frequency
45Hz~65Hz
Consumption
< 0.5VA
 Accuracy
0.5
 Output
 Display
LCD
 RS485 /C
Modbus-RTU 
 Alarm /J
the alarm of over voltage, under voltage and over current
 Analog /M
DC4~20mA, DC0~20mA (R < 600Ω), DC0~5V (R > 1kΩ) etc.
Pulse
2 pulse outputs (open-collector), 
Pulse constant : 15000 imp/kWh, 15000 imp/kvarh
 Logic
Input
2 or 4 dry contacts (with 5V power)
output
2 relays NO contact outputs (for remote terminal)
Contact capacity: 1A/30VDC, 1A/250VAC
Power supply
 Voltage range
AC85~265V or DC110-350V
Consumption
< 1.2W
 Insulation resistance
≥ 100MΩ
 Insulation
Power / Input / output 2kV/1min(RMS)
 ENV
Temperature
Operation: LCD: -10°C~+45°C; LED: -10°C~+55°C
Storage : -20°C~+70°C
Humidity
≤ 93%RH, no condensation,  without corrosive gas
Altitude
≤ 2500m