·Low initial resistance
Average arrestance:96%(ASHRAE52.1-1992)
Final resistance: (suggested) 400Pa
·Large dust holding capacity
·Flexible
·Outlet side with net or cloth
Application: capturing to particles, especially
for the top part of spray booth, prefiltration through
air filter program, diffluent equally
Type: supply pads or rolls size
Media: synthetic fiber with gradual density, full
imregnated with adhesive treatment
EN779 class: F5
Average arrestance:96%(ASHRAE52.1-1992)
Average efficiency: 45%-55 %(ASHRAE52.1-1992)
EUROVENT4/5 class: EU5
DIN53438 Non-flammability Standard: F1
Final resistance: (suggested) 400Pa
Max. Dust holding capacity: 480g/m2
Temperature resistance: 100degree
Instant temperature: ≤120degree
|
Type |
Dimensions |
Rated air velocity(m/s) |
Initial pressure drop (Pa)
|
Rated air flow(m2/h) |
||
|
Length(m) |
Width(m) |
Thickness(mm) |
||||
|
Rolls
|
14/21
|
1.6/2
|
22
|
0.25
|
40
|
900
|