Product Main

Specifications

TGas-1031 Series Combustible, Toxic and Harmful Gas Transmitter can continuously measure the concentration of site gas, and convert the concentration signal into 4-20mA output. It is extensively applied in petroleum, petrochemistry, chemical industry, gas, coal, metallurgy and electric power; safety detection in municipal administration, telecommunication and traffic tunnel construction; the place where combustible, poisonous and harmful gas might leak, such as gasholder station and special industrial factory building, etc.
 
Main features
l          Two kinds of optional mode of power supply, including centralized busbar type and independent area type
l          High and low concentration alarm, performing real-time monitor to gas
l          Anti-poisoning type gas sensor with high sensitivity
l          Automatic modification of ageing curve of sensor, keeping constant alarm sensitivity
l          Function of automatic recognition of sensor trouble, function of high concentration gas above-norm of sensor
l          Function of automatic detection at starting up, and it has advanced function of self-diagnosis and self-reparing.
l          The calibrated concentration value is adjustable, facilitating users to set by themselves
l          When the sensor loses the function of monitoring alarm because of ageing, the detector is capable of automatic recognition and alarm, so as to effectively avoid missing report.
 
Technical parameters
Parameters
Characteristics
Detectable gas
Combustible vapour of liquids, including methane, LPG, coal gas and gasoline, etc., as well as poisonous and harmful gas
Measurement precision
±5%F.S
Repeatability
2%
Measurement range
Refer to lectotype table for details
Drift
Zero drift: ±2%F.S
Range drift: ±5%F.S
Response time
<30s(T90)
Sampling method
Diffusion
Working environment
Temperature: -30℃ to 60℃; humidity: below 85% (no coagulation)
Remote control mode
By the adjustment mode by infrared remote control, the detector can be adjusted without opening of cover
4-20mA
output
4-20mA output corresponding to 0-100%, maximum load 800 ohms
Alarm output
The effective alarm is 1 point or 2 points; each alarm shall use SPDT electronic relay.
Contact rating of alarm relay:
Ohmic load: 5A@24Vdc or 120Vac or 240Vac
Inductive load: 50VA
Communication
Communication description: two-wire system parallel RS485 protocol, 32 points at most
Connection: Twisted pair with shield
Distance: maximum 1000m
Input voltage
24VDC±25%; power: 2W/way
Certificate
Explosion-proof grade: ExdIICT5
Protection class: IP66
Using cable
≥2.5mm2×4  Screened cable line, outside diameter of cable is required to be between 6mm- 9mm
 
 
Lectotype table for detected gas (part gas)
Model
Range
Low alarm setting range
High alarm setting range
Low alarm point
High alarm point
TGas-1031-FL
0-100%LEL
10%LEL-5%LEL
25%LEL-80%LEL
20%LEL
50%LEL
TGas-1031-CO
0-500ppm
25ppm-100ppm
100ppm-500ppm
35ppm
200ppm
TGas-1031-CO
0-1000ppm
25ppm-100ppm
100ppm-500ppm
35ppm
200ppm
TGas-1031-H2S
0-100ppm
5ppm-15ppm
15ppm-30ppm
10ppm
15ppm
TGas-1031-SO2
0-100ppm
1ppm-3ppm
3ppm-10ppm
2ppm
5ppm
TGas-1031-CL2
0-20ppm
3ppm-10ppm
5ppm-15ppm
5ppm
10ppm
TGas-1031-NH3
0-100ppm
20ppm-30ppm
30ppm-70ppm
25ppm
50ppm
TGas-1031-NO
0-250ppm
20ppm-50ppm
50ppm-100ppm
25ppm
50ppm
TGas-1031-NO2
0-100ppm
1ppm-2ppm
2ppm-5ppm
1ppm
2ppm
TGas-1031-HCN
0-30ppm
5ppm-10ppm
10ppm-15ppm
5ppm
10ppm
TGas-1031-PH3
0-1ppm
0.3ppm-0.5ppm
0.5ppm-0.8ppm
0.3ppm
0.6ppm
 
Executed standards.(GB Standard is China National Standard)
GB12358-2006 Gas monitors and alarms for workplace——General technical requirements
GB3836.1-2000 Electrical apparatus for explosive gas atmospheres——Part 1  General requirements
GB3836.4-2000 Electrical apparatus for explosive gas atmospheres—— Part 4  intrinsic safety "i"
Explosion-proof mark: ExiaIICT3, it applies to 0 zone, 1 zone and 2 zone, the place that contains IIA-IIC category and T1-T3 group of explosive gas mixture, and is qualified to get explosion-proof conformity certificate through inspection by CQST.