TGas-1031 Series Combustible, Toxic and Harmful Gas Transmitter can continuously measure the concentration of site gas, and convert the concentration signal into 4-20mA output. It is extensively applied in petroleum, petrochemistry, chemical industry, gas, coal, metallurgy and electric power; safety detection in municipal administration, telecommunication and traffic tunnel construction; the place where combustible, poisonous and harmful gas might leak, such as gasholder station and special industrial factory building, etc.
Main features
l Two kinds of optional mode of power supply, including centralized busbar type and independent area type
l High and low concentration alarm, performing real-time monitor to gas
l Anti-poisoning type gas sensor with high sensitivity
l Automatic modification of ageing curve of sensor, keeping constant alarm sensitivity
l Function of automatic recognition of sensor trouble, function of high concentration gas above-norm of sensor
l Function of automatic detection at starting up, and it has advanced function of self-diagnosis and self-reparing.
l The calibrated concentration value is adjustable, facilitating users to set by themselves
l When the sensor loses the function of monitoring alarm because of ageing, the detector is capable of automatic recognition and alarm, so as to effectively avoid missing report.
Technical parameters
|
Parameters
|
Characteristics
|
|
Detectable gas
|
Combustible vapour of liquids, including methane, LPG, coal gas and gasoline, etc., as well as poisonous and harmful gas
|
|
Measurement precision
|
±5%F.S
|
|
Repeatability
|
2%
|
|
Measurement range
|
Refer to lectotype table for details
|
|
Drift
|
Zero drift: ±2%F.S
Range drift: ±5%F.S
|
|
Response time
|
<30s(T90)
|
|
Sampling method
|
Diffusion
|
|
Working environment
|
Temperature: -30℃ to 60℃; humidity: below 85% (no coagulation)
|
|
Remote control mode
|
By the adjustment mode by infrared remote control, the detector can be adjusted without opening of cover
|
|
4-20mA
output
|
4-20mA output corresponding to 0-100%, maximum load 800 ohms
|
|
Alarm output
|
The effective alarm is 1 point or 2 points; each alarm shall use SPDT electronic relay.
Contact rating of alarm relay:
Ohmic load: 5A@24Vdc or 120Vac or 240Vac
Inductive load: 50VA
|
|
Communication
|
Communication description: two-wire system parallel RS485 protocol, 32 points at most
Connection: Twisted pair with shield
Distance: maximum 1000m
|
|
Input voltage
|
24VDC±25%; power: 2W/way
|
|
Certificate
|
Explosion-proof grade: ExdIICT5
Protection class: IP66
|
|
Using cable
|
≥2.5mm2×4 Screened cable line, outside diameter of cable is required to be between 6mm- 9mm
|
Lectotype table for detected gas (part gas)
|
Model
|
Range
|
Low alarm setting range
|
High alarm setting range
|
Low alarm point
|
High alarm point
|
|
TGas-1031-FL
|
0-100%LEL
|
10%LEL-5%LEL
|
25%LEL-80%LEL
|
20%LEL
|
50%LEL
|
|
TGas-1031-CO
|
0-500ppm
|
25ppm-100ppm
|
100ppm-500ppm
|
35ppm
|
200ppm
|
|
TGas-1031-CO
|
0-1000ppm
|
25ppm-100ppm
|
100ppm-500ppm
|
35ppm
|
200ppm
|
|
TGas-1031-H2S
|
0-100ppm
|
5ppm-15ppm
|
15ppm-30ppm
|
10ppm
|
15ppm
|
|
TGas-1031-SO2
|
0-100ppm
|
1ppm-3ppm
|
3ppm-10ppm
|
2ppm
|
5ppm
|
|
TGas-1031-CL2
|
0-20ppm
|
3ppm-10ppm
|
5ppm-15ppm
|
5ppm
|
10ppm
|
|
TGas-1031-NH3
|
0-100ppm
|
20ppm-30ppm
|
30ppm-70ppm
|
25ppm
|
50ppm
|
|
TGas-1031-NO
|
0-250ppm
|
20ppm-50ppm
|
50ppm-100ppm
|
25ppm
|
50ppm
|
|
TGas-1031-NO2
|
0-100ppm
|
1ppm-2ppm
|
2ppm-5ppm
|
1ppm
|
2ppm
|
|
TGas-1031-HCN
|
0-30ppm
|
5ppm-10ppm
|
10ppm-15ppm
|
5ppm
|
10ppm
|
|
TGas-1031-PH3
|
0-1ppm
|
0.3ppm-0.5ppm
|
0.5ppm-0.8ppm
|
0.3ppm
|
0.6ppm
|
Executed standards.(GB Standard is China National Standard)
GB12358-2006 Gas monitors and alarms for workplace——General technical requirements
GB3836.1-2000 Electrical apparatus for explosive gas atmospheres——Part 1 General requirements
GB3836.4-2000 Electrical apparatus for explosive gas atmospheres—— Part 4 intrinsic safety "i"
Explosion-proof mark: ExiaIICT3, it applies to 0 zone, 1 zone and 2 zone, the place that contains IIA-IIC category and T1-T3 group of explosive gas mixture, and is qualified to get explosion-proof conformity certificate through inspection by CQST.