Key Features
- Multi-setting, according to input power condition user can be set as 1/1, 1/3, 3/1 or 3/3 system.
- It’s designed with modular structure and is made up of 1-10 modules
- It’s fitted with redundancy and can be upgraded according to your specific requirements
- N+X redundant technique, thus ensuring the reliable performance of the system
- The batteries can be shared
- The input THDI is not more than 5%
- Out modular UPS is environmentally friendly, small in size and light in weight.
- It’s easy to maintain. The module can be replaced optionally.
- System controller is used to carry out communications and diagnosis.
- Uses centralized static switch module
Applications
Data processing centers, computer systems, servers, communication systems, financial systems, servers, communication systems, financial systems, traffic systems, medical systems, and many other fields.
Technical Specifications of Modular UPS, MPS9330 5KVA-210KVA
Model |
MPS9330 5KVA-210KVA |
Single module capacity |
5KVA 10KVA 15KVA |
System capacity |
5-210KVA |
Rated frequency |
50/60HZ |
Input |
|
Voltage range |
380/400/415V ± 20% |
Input mode |
3 phase 4 wire + ground wire / single phase 2 wire + ground wire |
Frequency range |
45Hz-55H |
Input power factor |
≥ 0.99 |
Total harmonic distortion |
<3% |
Slow start |
>60sec |
Output |
|
Voltage accuracy |
220V (Single phase) 380/400/415V (3 phase) |
Frequency accuracy |
When the frequency of utility power is 50HZ±2%, the output frequency of UPS follows the utility power frequency, and the phase difference is < 3°; when the frequency of utility power is beyond the 50Hz±0.2% or when the battery offers power, the output frequency is 50Hz±0.2%. |
Power factor |
0.8 |
Harmonic Distortion |
Linear load ≤3% , non-linear load ≤5% |
Current Crest Ratio |
3:1 |
Whole unit efficiency |
≥95% (AC power) ≥98% (Battery Powered) |
Current sharing accuracy |
≤5% |
Transfer time |
0ms |
Dynamic response transient range |
Overload 10%~100% or 100%~10%, the output voltage is ≤2% |
Load unbalance capability |
Can endure 100% unbalanced load |
DC |
|
Input rated voltage |
±384V |
Input voltage range |
345V~440V |
Panel display |
|
LCD |
Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning. |
Working environment |
|
Temperature |
0~40℃ |
Humidity |
0~95%, non-condensing |
Storage temperature |
-25℃~55℃ |
Altitude |
≤ sea level 1500m |
Noise(within 1m) |
< 50dB |
Physical property |
|
Size W × D× H(mm) |
600 × 800 × 2000 |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943
Note: Product specifications are subject to change without further notice.
UPS Modules
- Expansion easily according to demand to choose capacity collocate
- Online double conversion design, assure the output quality.
- Every module has digital and intelligent control separately.
- Every module just and independent UPS, can work independently.
- Every module has independent charging system.
- Hot swappable, it ensure online maintenance.
- Standard dimension: 2U × 19 × 520mm
Static Switches
- Static Switch module for standard mode UPS.
- Work in SCR and AC contactor paralleled.
- High reliability, high overload ability: 100%, 1 second, 0ms transfer times.
- Function of self-diagnosis, interlock, protection
Communication & Monitoring Module
- System data.
- Modules data
- History log
- Work state display alarm and communication
- RS232 and RS422
- 8-pulse dry contacts output.
- SNMP adapter for standard mode.