Key Features
1. Full digital control technique
2. Intelligent detecting and monitoring function
3. Digital control static switch and zero changeover time
4. Full isolation between input and output
5. DC panel and utility power are full isolated.
6. Uses electric power standard cabinet.
7. It’s provided with over voltage protection, under voltage protection, over current protection, short circuit protection and some other protection functions.
8. Large LCD can display the input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and other running conditions in Chinese and English.
9. At most 256 pieces of historic records can be showed. This makes it easier for users to analyze the power supply condition.
10.The static state bypass has strong anti-overload capacity.
Applications
Chemical factories, Power generating plants, Power distribution stations, electrical substations, electric power communication systems, and many other fields.
Technical Specifications of Industrial UPS DTS9310 Series
DTS9310 6-80KVA |
||||||||||
6KVA |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
||
Rated Capacity |
6KVA/ 4.8KW |
10KVA/ 8KW |
15KVA/ 12KW |
20KVA/ 16KW |
30KVA/ 24KW |
40KVA/ 32KW |
50KVA/ 40KW |
60KVA/ 48KW |
80KVA/ 64KW |
|
Rated Voltage |
220V Single Phase (6-20KVA)/380VA |
|||||||||
Rated Frequency |
50/60HZ |
|||||||||
AC Input |
||||||||||
Voltage range |
±20% |
|||||||||
Frequency range |
50/60HZ±10% |
|||||||||
Soft start |
0-100% 5sec |
|||||||||
Power factor |
0.95 (with input filter) |
|||||||||
Bypass input |
||||||||||
Voltage range |
15% |
|||||||||
Frequency range |
50/60HZ±5% |
|||||||||
|
|
|||||||||
Output |
||||||||||
Voltage accuracy |
220V±1% (Steady state load) 220V±3% (load fluctuation) |
|||||||||
Frequency accuracy |
50/60Hz±0.05Hz (Battery supply power) |
|||||||||
Power factor |
0.8 |
|||||||||
Harmonic distortion |
Linear load<2%; non-linear<4% |
|||||||||
Dynamic state load voltage transient |
<5% |
|||||||||
Current crest ratio |
3:1 |
|||||||||
Overload Capacity |
110% load work normally;125%10min; 150%1min; |
|||||||||
Efficiency |
Double conversion mode: 94% , ECO mode : 98% |
|||||||||
DC |
||||||||||
Nominal Battery Voltage |
220V |
|||||||||
Cutoff voltage |
185V |
|||||||||
Maximum discharge current |
21A |
36A |
55A |
73A |
109A |
145A |
181A |
218A |
291A |
|
Panel display |
||||||||||
LCD |
Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning. |
|||||||||
Working environment |
|
|||||||||
Temperature |
0-40℃ |
|||||||||
Humidity |
0-90%, non-condensing |
|||||||||
Storage temperature |
-25℃-55℃ |
|||||||||
Altitude |
<1500m lower than sea level |
|||||||||
Physical property |
||||||||||
Weight (KG) |
N.W |
230 |
258 |
350 |
400 |
480 |
580 |
650 |
900 |
950 |
G.W |
250 |
285 |
280 |
425 |
500 |
600 |
675 |
925 |
988 |
|
Size W × D× H(mm) |
800×600×2260 |
|||||||||
Option |
RS485/network adapter (SNMP)/harmonic compensation tank/input and output power distribution cabinet/input and output isolation cabinet/lightning protection device/bypass voltage regulation cabinet/ the cabinet size can be customized. |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943