Product Main

Specifications

Key Features
1. Full digital control technique
2. Intelligent detecting and monitoring function
3. Digital control static switch and zero changeover time
4. Full isolation between input and output
5. DC panel and utility power are full isolated.
6. Uses electric power standard cabinet.
7. It’s provided with over voltage protection, under voltage protection, over current protection, short circuit protection and some other protection functions.
8. Large LCD can display the input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and other running conditions in Chinese and English.
9. At most 256 pieces of historic records can be showed. This makes it easier for users to analyze the power supply condition.
10.The static state bypass has strong anti-overload capacity.
Applications
Chemical factories, Power generating plants, Power distribution stations, electrical substations, electric power communication systems, and many other fields.

Technical Specifications of Industrial UPS DTS9310 Series

Model

DTS9310  6-80KVA

6KVA

10KVA

15KVA

20KVA

30KVA

40KVA

50KVA

60KVA

80KVA

Rated Capacity    

6KVA/

4.8KW

10KVA/

8KW

15KVA/

12KW

20KVA/

16KW

30KVA/

24KW

40KVA/

32KW

50KVA/

40KW

60KVA/

48KW

80KVA/

64KW

Rated Voltage

220V Single Phase (6-20KVA)/380VA

Rated Frequency

50/60HZ

AC Input

Voltage range

±20%

Frequency range

50/60HZ±10%

Soft start

0-100%   5sec

Power factor

0.95 (with input filter)

Bypass input

Voltage range

15%

Frequency range

50/60HZ±5%

 

 

Output

Voltage accuracy

220V±1% (Steady state load)  220V±3% (load fluctuation)

Frequency accuracy

50/60Hz±0.05Hz (Battery supply power)

Power factor

0.8

Harmonic distortion

Linear load<2%; non-linear<4%

Dynamic state load voltage transient

<5%

Current crest ratio

3:1

Overload Capacity

110% load work normally;125%10min; 150%1min;

Efficiency

Double conversion mode: 94% , ECO mode : 98%

DC

Nominal Battery Voltage

220V

Cutoff voltage

185V

Maximum discharge current

21A

36A

55A

73A

109A

145A

181A

218A

291A

Panel display

LCD

Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning.

Working environment

 

Temperature

0-40℃

Humidity

0-90%, non-condensing

Storage temperature

-25℃-55℃

Altitude

<1500m lower than sea level

Physical property

Weight (KG)

N.W

230

258

350

400

480

580

650

900

950

G.W

250

285

280

425

500

600

675

925

988

Size W × D× H(mm)

800×600×2260

Option

RS485/network adapter (SNMP)/harmonic compensation tank/input and output power distribution cabinet/input and output isolation cabinet/lightning protection device/bypass voltage regulation cabinet/ the cabinet size can be customized.

Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2  GB/17626.2~5/IEC61000-4-2~5     SAFETY:GB4943