Specifications
-
Technical parameters:
-
Pipe diameter applied to DN6 to 600mm
-
Precision: ±1%FS
-
Repeatability: 0.3%
-
Flow range: 0.5 to 6m/s
-
Minimum pipe Reynolds number can be measured: Re=4,500
-
Fluid temperature: -20 to 100°C
-
Environment temperature: +20 to 180°C
-
Common type: -25 to 55°C
-
Explosion proof type: -20 to 40°C
-
Fluid pressure: stainless steel body
-
Welding installation: ≤10mPa
-
Saddle support installation: ≤2mPa
-
Glass fiber filled polyvinylidene fluoride body ≤1.2mPa (at 20°C) ≤0.15ma (at 90°C)
-
Installation: welded, saddle support, Y-joint type, quick unload (below 25mm) and thread connection type (below 25mm)
-
Various types of pre-amplifiers are provided
-