Product Main

Specifications

OB16-63 Mini Circuit Breaker (MCB) detailed information for you:
Number of poles: 1P1P+N2P3P3P+N4P
Mini Circuit Breaker Rated Voltage(Un): AC 230(240)/400(415)V
Short-circuit breaking capacity(Icn):10000A (10kA)
Application scope:
The product is used to circuit with rated voltage up 400V AC, rated frequency 50/60Hz and rated current up to 63A for protection and control of circuit against overload and short circuit in commercial, household and electric equipment installation. The product is fit for non-frequently making and breaking operation.
The product can be operated by non-professionals and it is free of maintenance.
Standard
GB10963
IEC60898
Construction features:
Circumstance temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
·Altitude above sea level less than 2000 m.
·Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
·Installation class II or III.
·Pollution class 2.
·Installation method DIN Rail mounting type.
·The external magnetism shall be less than 5 times of terrestrial one.
·Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.

Order note :
1.Minimum order quantity, time during the order to delivery;
2.Need to indicate type , specification , rated current , number of poles, quantity of the products while ordering.
 
Normal operation and mounting requirement:
·Circumstance temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
·Altitude above sea level less than 2000 m.
·Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
·Installation class II or III.
·Pollution class 2.
·Installation method DIN Rail mounting type.
·The external magnetism shall not be more than 5 times of terrestrial one.
·Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.
 
Main technical parameters:

Type OB16-63 MCB
Number of poles 1P1P+N2P3P3P+N4P
Rated Current(In) 123461016202532405063A
Rated Voltage(Un)
AC 230(240)/400(415)V
Rated frequency 50(60)Hz
Curve BCD
Short-circuit breaking capacity(Icn) 10000A (10kA)
Magnetic releases operate B curve: between 3 and 5 In
C curve: between 5 and 10 In
D curve: between 10 and 20 In
Endurance ≥ 4000
Terminal protection IP2LX