Product Main

Specifications

Rated current (A): 6,10,16,20,25,32
No.of pole: 1+N
Rated voltage (V): 230V
Rated current of frame: 32

 
Application
DPNL RCBO is used in the single phase residence circuit of AC 50Hz/60Hz,rated voltage 230V,used as electron shock protection.It can protect civil electron circuit form overload and short circuit This product has advantages of small volumn,high breaking capacity zero,and live wire are cut off at the same time,also protecting person from electric shock when the live wire connected opposite.This product conforms to IEC61009,GB16917 Stardands.
Main Technical Paramete
Rated
current (A)
No.of
pole
Rated
voltage (V)
Rated current of
frame
Rated leakage
operating
Rated leakage non-operating current
Rated
leakage breaking time
Breaking
capacity (A)
6,10,16,
20,25,32
1+N
230
32
30
15
≤0.1s
3000

Overload Trip Characteristic
Rated
current(A
Rated
voltage(A)
Limited
time
Pre-engage
result
Start state
Note
1.13In
all
t≥1h
non-trip
cold state
 
1.45In
all
t<1h
trip
heat state
he current rise steadily to a fixed #118alue within 5s
2.55In
all
1
non-trip
cold state
 
5In
all
t≥0.1s
trip
old state
Open the supplementary switch,connect the power
10In
all
t<0.1s
trip
old state
Open the supplementary switch,connect the power