Product Main

Specifications

Rated Voltage (V): 220V,380V
Rated current (A):110A
Leakage action current (mA): 30 , 100
Leakage dead current (mA):15 , 50

 
Application
DZ47LE Residual Current Operated Circuit Breaker with overcurrent protection(RCBO)  is used for the protection,against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 240V, 3 phase 415V, rated current up to 60A. When somebody gets an electric shock or the residual current of the circuit exceeds the fixed #118alue, the ELCB can cut off the power within the time of 0.1s automatically protecting the personal safety and preventing the equipement from the fault resulted from teh residual current. With this function, the ELCB can protect the circuit against overload and short circuit or can be used for the unfrequent switch over of the circuit under normal conditions.It conforms to IEC60898 & IEC60755.
Specification
Rated
Voltage (V)
Pole No
Rated current (A)
Leakage action current (mA)
Leakage
dead
current (mA)
Leakage action
time(s)
220V
1P
110
30
15
<0.1
1532
380V
2,3,4P
 
100
50

a.TH35-7.5 rail is used for the product installation.
b.Outline and installation dimensions(see the figure and the table)
Type
Dimensions
A
B
C
D
E
 DZ47LE-60/1N
46
70
40
45
94
DZ47LE-60/2
64
70
40
45
94
DZ47LE-60/3
91
70
40
45
94
DZ47LE-60/3N
100
70
40
45
94
DZ47LE-60/4
118
70
40
45
94