DZ108 moulded case circuit breaker is suitable in AC circuit of 50Hz or 60Hz, voltage up to 660V and current up to 0.1-63A.
DZ108(3VE)series moulded case circuit breaker(MCCB) is suitable in AC circuit of 50Hz or 60Hz, voltage up to 660V and current up to 0.1-63A and used toprevent small capacity motor and circuit from overload and short circuit and also used as direct starter forstarting the motor and a switch for changeover the circuit under normal conditions.
Specification
Type | DZ108-1(3VE1) | DZ108-3(3VE3) | DZ108-4(3VE4) | |
Poles | 3 | 3 | 3 | |
Rated current (A) | 20 | 32 | 63 | |
Rated voltage (V) | 660 | 660 | 660 | |
Rated insulation voltage (V) | 660 | 750 | 750 | |
Current setting voltage (V) |
0.1~0.16 0.16~0.2 5 0.25~0.4 0.4~0.63 0.63~1 1~1.6 1.6~2.5 2~3.2 2.5~4 3.2~5 4~6.3 5~8 6.3~10 8~12.5 10~16 14~20 |
1~1.6 1.6~2.5 2.5~4 4~6.3 6.3~10 8~12.5 10~16 12.5~20 16~25 22~32 |
6.3~10 10~16 16~25 22~32 28~40 36~50 45~63 45~56 |
|
Power of controlled motor (KW) | 220V | 5.5 | 9 | 18 |
380V | 10 | 16 | 32 | |
660V | 13 | 26 | 58 | |
Mechanical life(1×104) | 10 | 10 | 3 | |
Protective feature | 1.05le | Not act within 2hrs | ||
1.2le | Act within 2hrs | |||
12le | Action snap |