•Universally PC programmable (PCP)
•Galvanic isolation
•2 wire technology, 4 to 20 mA analog output
•High accuracy in total ambient temperature range
•Fault signal on sensor break or short circuit
•Configuration during measurement using configuration kit
•Output simulation
•Customer specific measurement range setting
• PC programmable (PCP) Temperature head transmitter
for converting various input signals into a standard 4 to 20 mA analogue output signal
• Input:
-Resistance thermometer (RTD)
-Thermocouple (TC)
-Resistance transmitter (Ohm)
-Voltage transmitter (mV)
• Online configuration using a PC with MS181 configuration kit (MS181-PC)
Primary Technical Characteristics
Programmable Use the MS181 programming tool
Measuring range Set via PC
PC Interface USB/RS232
Input type RTD, TC, R or Millivolt signal
Convert accuracy ≤0.1%FS
Cold junction accuracy ±1℃(TC)
Output 4~20mA/20~4mA Electrical isolation output
Max-load (V -8V)/0.025A(Current output )
Limit current ≤25mA
Response time 1s
Isolated voltage 1500V AC (input/output)
Alarm signal Programmable
Long-term stability ≤0.1℃ per year or 0.05% per year
Ambient -40~+85℃