MS181 is an intelligent temperature transmitter module which can be programmed through a PC with Configuration Kit. It has measurement input for resistance thermometers (RTD) ,thermocouples, resistances or millivolt signals in 2-,3- or 4-wire connection, and converts various input signals into a 4~ 20mA analog output signal after linear processing. Isolation is provided between the input and output. A special signal can be set in advance while the sensor burnout or short.
Primary Technical Characteristics
Programmable Use the MS181 programming tool
Measuring range Set via PC
PC Interface USB/RS232
Input type RTD, TC, R or Millivolt signal
Convert accuracy ≤0.1%FS
Cold junction accuracy ±1℃(TC)
Output 4~20mA/20~4mA Electrical isolation output
Max-load (V -8V)/0.025A(Current output )
Limit current ≤25mA
Response time 1s
Isolated voltage 1500V AC (input/output)
Alarm signal Programmable
Underranging linear drop to 3.8 mA
Overranging linear rise to 20.5 mA
Sensor break or short-circuit:≤3.6mA or≥21.0mA
Power supply 8~30V DC
Temperature drift 0.01% FS / 1℃
Long-term stability ≤0.1℃ per year or 0.05% per year
Ambient -40~+85℃