380V Active Power Filter
Technical Parameters
|
Bestern-APF-75-380 / Bestern-APF-100-380
|
Rated Compensation Current
|
75 / 100
|
Dimensions(H*W*D mm)
|
232*440*575
|
Net Weight (kg)
|
50
|
Installation
|
Wall-mounting / Rack
|
Line Lead-in
|
Top / Back
|
Cooling Method
|
Smart air cooling, 151L / Sec
|
Noise Index
|
<56dB
|
Protection Degree
|
IP20
|
Quantity of Sets
In Combination
|
Not Limited
(recommend:six sets at most)
|
CT Mutual Inductor(open)
|
150 / 5 ~ 6000 / 5
|
Instructions:
Applicable to three –phase three-wire and three-phase four-wire system.
Confirm the compensation current via real-time data or use the electricsystem (current transformer and load) to calculate the compensation current.
3-phase 4-wire system needs 3 CTs (for phase A,B and C)
3-phase 3-wire system needs 2 CTs (for phase A and C)
Technical Parameters
Model
|
25A ~ 100A
|
Rated Compensation Capacity
|
25A / 100A
free combinaton and capacity extend
|
Working Voltage (V)
|
380 - 40% ~ +20%
|
Working Frequency (Hz)
|
50 / 60 + / -10%
|
Entire Efficiency
|
> 97%
|
Filtering Ability
|
THDi < 5%
|
Filter Range
|
2-50 times
|
Fast Response Time
|
< 300 µs
|
Full Response Time
|
< 10 ms
|
Neutral Line Filtering Ability
|
3 times better than phase line
|
IGBT Frequency
|
20KHz
|
Self-checking
|
Yes
|
Communication Interface
|
Rs485, network port
|
Communication Protocol
|
Power of the General Agreement
Modbus agreement
|
Ambient Temperature
|
0°C ~ 40°C
|
Storage Temperature
|
-40°C ~ 70°C
|
Relative Humidity
|
Max 95%, no condensation
|
Altitude
|
≤1500m,according to GB/T3859.2, power decrease one percent when 100m more added from 1500 to 4000.
|