Product Main

Specifications

APC Smart-UPS On-Line, 700 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model, Rack Height 2 U
Includes  CD with software, Smart UPS signalling RS-232 cable, User Manual
Standard Lead Time: Usually in Stock

Output
Output Power Capacity : 700 Watts / 1000 VA 
Max Configurable Power : 700 Watts / 1000 VA
Nominal Output Voltage : 230V
Waveform Type : Sine wave
Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load : 88%
Output Voltage Distortion : Less than 3% at full load
Output Frequency (sync to mains) : 50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor : 3 : 1
Output Connections :
(6) IEC 320 C13   
(2) IEC Jumpers 
 
Bypass : Built-in Bypass
Nominal Input Voltage : 230V
Input Frequency : 50/60 Hz +/- 5 Hz (auto sensing)
Input Connections : IEC-320 C14 

Input voltage range for main operations : 160 - 280V
Input voltage adjustable range for mains operation : 100 - 280V
Other Input Voltages 220,240
Communications & Management
Interface Port(s) : DB-9 RS-232,SmartSlot
Available SmartSlot™ Interface Quantity : 1
Control panel : LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO) : Optional
Surge Protection and Filtering
Surge energy rating :420 Joules
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height : 432.00 mm
Maximum Width : 85.00 mm
Maximum Depth : 483.00 mm
ck Height : 2U
Net Weight : 23.00 KG
Shipping Weight : 27.80 KG
Shipping Height : 286.00 mm
Shipping Width : 630.00 mm
Shipping Depth : 594.00 mm
Color :Black 
Units per Pallet : 12.00
Environmental
Operating Environment : 0 - 40 °C
Operating Relative Humidity : 0 - 95%
Operating Elevation : 0-3000 meters
Storage Temperature : -20 - 45 °C
Storage Relative Humidity :0 - 95%
Storage Elevation :0-15000 meters
Audible noise at 1 meter from surface of unit :55.00 dBA
Online Thermal Dissipation : 324.00 BTU/hr
Conformance

Regulatory Approvals : C-tick,CE,EN 50091-1,EN 50091-2,EN 55022 Class A,EN 60950,EN 61000-3-2,GOST,VDE
Standard Warranty : 2 years repair or replace,optional on-site warranties available,optional extended warranties available 
Environmental Compliance : RoHS 7b Exemption 
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS