Fan and filter Type: FK
|
6625.230
|
6625.115
|
6625.024
|
Designed working voltage V/H
|
230/50/60
|
115/50/60
|
24(DC)
|
Air flow, free blowing
|
230/265 m3 /h
|
||
Flux of air equip filter exported Include filtering pad of standard
|
1× FK 6625.300: 170/205 M3 /H
2× FK 6625.300: 200/230 M3 /H 1× FK 6625.300: 190/215 M3 /H |
||
Axial fan
|
Self-start screened magnetic pole motor
|
Direct current motor
|
|
Rated current
|
0.28A/0.24A
|
0.53A/0.49A
|
0.58A
|
power
|
41W/38W
|
41W/38W
|
14W
|
Noise level
|
46/49dB(A)
|
||
Scope of temperature
|
-10~+55
|
||
Exit filter Type: FK
|
6625.300
|
||
It is possible to write to our company to consult if needing special voltage.
|
Product Description
Only when the temperature in cabinet is higher than the environmental temperature, use the filter fan can taking effective. Normally, the front door or the place under side wall plate of the cabinet should be use as air inlet, the upper use as air outlet, for the warm air is lighter than cold air, the flow path of the air in cabinet should be from up to down.
We launched a typical configuration for you: Use a filter fan in the air inlet, choose a vent selection filters in air outlet. Selection can be in accordance with environment and heat loss in cabinet, also can be done in the form of filter fan characteristic curve.
No need for Installation tools:
Filter fan is different from others, beautiful, good performance, safe, latch-locked installation of the filter fan make the installation as simple as a children's game, its unique design, make it can meet the market requirements best, fast installation and high efficiency.