Split Core Current Transformers has been specially designed to facilitate their installation in new or already existing net works. They may be installed without opening any cable or bus-bar circuit. The connection of conventional CTs usually requires the interruption of the primary side circuit to pass cables or bur-bars through the transformer core or to connect such cables to the primary terminals.
The transformers core may be easily opened and they may be installed and connected without any supply interruption. Thus saving time and the installation costs
                  spec
  model
Outside dimension Though hole dimension Install dimension
W H D a e M N
K-30× 20 90 114 40 22 32 50 49.5
K-80× 50 114 159 36 52 82 78 49.5
K-80× 80 144 159 36 82 82 108 49.5
K-120× 80 144 199 36 82 122 108 49.5
K-160× 80 184 254 52 82 162 120 49.5
model ratio(A) accuracy Rated burden  ( VA  )
K-30× 20 100/5 1.0 1.0
150/5 1.0 1.0
200/5 0.5 1.5
250/5 0.5 1.5
300/5 0.5 1.5
400/5 0.5 2.5
K-80× 50 250/5 1 1.5
300/5 1 1.5
400/5 0.5 1.5
500/5 0.5 2.5
600/5 0.5 2.5
750/5 0.5 2.5
800/5 0.5 2.5
1000/5 0.5 5
K-80× 80 250/5 1 1.5
300/5 1 1.5
400/5 0.5 1.5
500/5 0.5 2.5
600/5 0.5 2.5
750/5 0.5 2.5
800/5 0.5 2.5
1000/5 0.5 5
K-120× 80 500/5 0.5 2.5
600/5 0.5 2.5
750/5 0.5 2.5
800/5 0.5 2.5
1000/5 0.5 5
1200/5 0.5 7.5
1250/5 0.5 7.5
1500/5 0.5 7.5
K-160× 80 1000/5 0.5 5
1500/5 0.5 10
2000/5 0.2 15
2500/5 0.2 15
3000/5 0.2 20
4000/5 0.2 20
5000/5 0.2 20