Product Main

Specifications

GAS AGENRATOR TYPE: 200kw Gas Generator /natural gas geneator/bio gas generator
;200kw Gas Generator;gas generators;gas powered generator;gas home generator;gas generator;

 
 
Description
Model
Dimension (mm) L×B×H
Net Weight (kg)
Instruction
200GF-RG/PwG
5300×1970×2250
8100
Open cooling method for heat exchanger
4510×1970×2260
7500

Closed cooling method for horizontal water box with more than one fan

 
Technical Parameters
Name of Parameter
Value of Parameter
Model of the set
200GF-RG
200GF-PwG
Model of gas engine
G6190ZLDK-2A
Model of generator
1FC6 354-6LA42
Rated power(kW)
200
Rated current(A)
288
Rated voltage(V)
400
Rated frequency(Hz)
50
Rated rotated speed(r/min)
1000
Rated power factor(cosφ)
0.8(lag)
The number of phase and the wiring method

Three coils wired by three phase lines or three coils wired by three phase lines and one zero line.

Way for adjusting pressure
Automatic adjusting pressure
Excitation method
Brushless excitation
Starting up method
24VDC Electric starting system
Technical Parameters
Name of Parameter
Value of Parameter
Model
G6190ZLDK-2A
Number of cylinder
6
Arranging way of cylinders
Straightly arranged
Diameter of cylinder(mm)
190
Route(mm)
210
Total displacement(L)
35.73
Air inflow way

Increasing the pressure by using the exhaust produced by the generator to promote the operation of the turbine, thus improve the inlet pressure. The intercooler for air inflow is also used.

Rated power(kW)
210
Rated rotate speed(r/min)
1000
Min. stable rotate speed with empty load(r/min)
600
Dimension(L×B×H) (mm)
3226×1120×2005
Net weight(kg)
4500
 

Conditions for Using
1. Temperature of the straw gas should not surpass 40â?? when it is 1m or nearer to the pressure regulating valve for air inflow.
2. The pressure that this biomass generator set can sustain ranges from 3kPa to 10 kPa and the fluctuated frequency of the pressure should not surpass 1kPa/min.
3. The granularity of the impurity should not surpass 5 μm and its max. content is 30mg/Nm3.
4. For the straw gas used in this biomass generator set, the volume content of H2 should not surpass 20% and the max. content of H2S, NH3 and tar are 50mg/Nm3, 20mg/Nm3, and 50mg/Nm3.
5. The moisture content in straw gas should not surpass 40g/Nm3 and the heating value of the gas should not be lower than 4MJ/Nm3.
For gas that cannot reach the conditions above, special allocation will be tookfor this biomass generator set after evaluation according to the specific composition, pressure, temperature, etc. provided.

Technologies Used
This biomass generator set uses electrically fuel gas mixing technology, low-pressure air inflow technology, automatic control technology for burning and safe conveying system.