CJ-F 1000 Series Conventional Fire Alarm Control Panel
 
Model: CJ-F1004, CJ-F1008, CJ-F1016
 
The CJ-F1000 Series Conventional Fire Alarm Control Panel is a 24 volt, four, eight, sixteen-zone, Class B, Conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly cost-effective CJ-F1000 Series can be used in a variety of low- to mid-sized applications.
 
FEATURES                                                                                                                                                                         
Four to Sixteen Style B (Class B) Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
Zones 1 - 16 configured as general alarm zones.
All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology.
Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
NACs may be programmed:
Silenceable.
Non-Silenceable.
Auto-Silence (program 5 to 20 minutes).
1.25 amps of NAC power.
3.0 amps of total system power.
Alarm, Trouble and Supervisory, relay output.
24-volt operation.
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require use of the external battery backbox, or ULC listed equivalent).
Disable/Enable control per IDC.
Reverse polarity protection.
Control buttons:
Mode
Test
ACK (Acknowledge) Alarm Silence
Reset
LED indicators:
AC Power(green & yellow LED)
Fire Alarm(red LED)
Trouble(yellow LED)
Supervisory(yellow LED)
Signal Silence(yellow LED)
Battery Power(green & yellow LED)
Zone Disable(yellow LED)
NAC Fault(yellow LED)
NAC Disable(yellow LED)
Zone Alarm(one for each zone) (red LED)
Zone Trouble(one for each zone) (yellow LED)
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
 
SPECIFICATIONS                                                                                                                                                             
AC POWER
90~270 VAC, 50 Hz, 2.0 amps.
Wire size: minimum 14 AWG (2.0 mm2) with 600-volt insulation.
BATTERY
Sealed lead-acid batteries only.
Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge.
Maximum battery charger capacity: 18AH battery.
NOTE: two 4AH batteries can be housed in the cabinet. Larger
batteries require a separate battery box.
Total 24 V system power: 3.0 amps.
Notification appliance (signal) power: 2.5 amps.
Maximum current per NAC: 1.25 amps (expandable to 2.5amps).
Maximum battery charging capability: 18 AH.
Auxiliary Outputs
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
NOTE: Total current for auxiliary power outputs and two NACs must not exceed 3.0 amps. .
Integral Form-C Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30VAC (resistive).
 
CABINET AND MOUNTING
CABINET PHYSICAL DIMENSIONS: 40.0 cm high x 35.0 cm wide x 11.5 cm deep.
CARTON PACKAGE DIMENSIONS: 48.0 cm high x 42.0 cm wide x 18.5 cm deep.
CABINET NET WEIGH: 6.0 Kg. (without batteries).
CABINET GROSS WEIGH: 6.6 Kg. (without batteries).
MOUNTING: The cabinet mounts using two key slots at the top of the back and two additional 6.5mm diameter holes at the bottom.