Product Main

Specifications

Detailed Product Description
 
Overhead Insulated Cables according to DIN 48201 BS 6485

 
 
Nominal Area
Calcu- lated Area
Wires
Approx. Overall Diameter
Nominal Breaking Load
Nominal DC Resistance at 20°C
Approx. Weight
Approx. Overall Diameter
Approx. Total Weight
Packing Length
No.
Dia.
mm²
mm²
 
mm
mm
KN
Ohm/km
kg/km
Mm
kg/km
(M+/-5%)
10
10.02
7
1.35
4.1
4.02
1.8055
90
6.1
115
2000
16
15.89
7
1.70
5.1
6.37
1.1386
143
7.1
174
2000
25
24.25
7
2.10
6.3
9.72
0.7461
218
8.3
256
2000
35
34.36
7
2.50
7.5
13.77
0.5265
310
9.5
355
1000
50
49.48
7
3.00
9
19.84
0.3656
446
11.0
501
1000
 
50
48.35
19
1.80
9
19.38
0.376
437
11.0
490
1000
70
65.81
19
2.10
10.5
26.38
0.2762
596
12.5
658
1000
95
93.27
19
2.50
12.5
37.39
0.1949
845
14.5
920
1000
120
116.99
19
2.80
14
48.90
0.1554
1060
16.0
1145
1000
 
150
147.11
37
2.25
15.8
58.98
0.1238
1337
17.8
1430
1000
185
181.62
37
2.50
17.5
72.81
0.1003
1649
19.5
1748
1000
240
242.54
61
2.25
20.3
97.23
0.0753
2209
22.5
2338
1000
300
299.43
61
2.50
22.5
120.04
0.061
2725
24.7
2870
1000
400
400.14
61
2.89
26
160.42
0.0456
3640
28.2
3810
500
500
499.83
61
3.23
29.1
200.38
0.0365
4545
31.3
4739
500
Overhead Insulated Cables