NS series moulded case circuit breaker/mccb  is suitable for using in the circuit of AC 50Hz/60Hz, rated insulating voltage 750V, rated working voltage below 690V, and rated current is 12.5A to 1600A for distributing electric energy,and infrequently off/on under normal condition.The short circuit breaking capacity is 18KA---150KA. Have 1pole,2pole,3pole,4poles.
 
Specification
 
Type
Rated current
(A)
Poles
Rated insulating voltage
(V)
Rated operating voltage
(V)
Arcing over distance
(mm)
Utimate short circuit breaker capacity
Servies short circuit breaker capacity
Operating performance (times)
NS-100D
12.5,16,20,
25,32,40,50,
63,80,100
3,4
950
690
0
18
18
1500,8500
NS-100N
25
25
NS-100H
70
70
NS-100L
150
150
NS-160D
16,20,25,32,
40,50,63,80,
100,125,160
25
25
1500,7000
NS-160N
36
36
NS-160H
70
70
NS-160L
150
150
NS-250D
160,180,
200,225,250
25
25
1000,7000
NS-250N
36
36
NS-50H
70
70
NS-250L
150
150
NS-400D
200,225,250,
300,315,400
35
35
1000,4000
NS-400N
45
45
NS-400H
70
70
NS-400L
150
150
NS-630D
315,250,400,
500,600,630
35
35
10004000
NS-630N
45
45
NS-630H
70
70
NS-630L
150
150
 
TRIPPING CHARACTERISTICS OF MCCB:
 
Rated current of release (A)
Thermodynamic release (ambient temp +40℃)
Operational current of magnetic release (A)
1.05In (cold state) inoperative time(h)
1.30In (heat state) inoperative time (h)
In≤63
≥1
<1
10In±20%
63<In≤100
≥2
<2
10In±20%
100<In≤630
≥2
<2
5-10In±20%
 
 
 
Rated current of release (A)
Thermodynamic release (ambient temp +40℃)
Operational current of magnetic release (A)
1.0In (cold state) operative time(h)
1.20In (heat state) operative time (h)
1.50In (heat state) operative time (h)
1.01In (heat state) operative time (h)
12.5≤In≤400
≥2
<2
4≤min
2S<TP≤10
12In±20%