Geothermal Heat Pump Details
1.Cooling Capacity Testing Working Condition: User Side Chilled water inlet/outlet 12°C/7°C;Source water side inlet/outlet 18°C/29°C;
1.Cooling Capacity Testing Working Condition: User Side Chilled water inlet/outlet 12°C/7°C;Source water side inlet/outlet 18°C/29°C;
2.Heating Capacity Testing Working Condition:User Side hot water inlet/outlet 40°C/45°C;Source water Side inlet/outlet 15°C/7°C;The max hot water temperature output 65°C(Refrigerant R134a).
|
Unit Model LTMLH(R)-
|
70
|
85
|
110
|
150
|
185
|
220
|
260
|
310
|
375
|
440
|
515
|
615
|
750
|
885
|
1000
|
|||
|
Heating Capacity(KW)
|
260
|
317
|
408
|
567
|
694
|
816
|
951
|
1134
|
1388
|
1632
|
1902
|
2268
|
2777
|
3264
|
3805
|
|||
|
Cooling Capacity(KW)
|
247
|
300
|
387
|
536
|
657
|
775
|
900
|
1072
|
1315
|
1550
|
1800
|
2145
|
2630
|
3100
|
3600
|
|||
|
Electrical
Parameter |
Power
|
3/N/PE AC380V/220V 50HZ
|
||||||||||||||||
|
Input
|
Cooling
|
kW
|
42.6
|
52.1
|
66.8
|
92
|
112.3
|
130.2
|
151.3
|
184
|
224.6
|
260.4
|
302.6
|
368
|
449.2
|
520.8
|
605.2
|
|
|
Power
|
Heating
|
kW
|
58.2
|
71.1
|
91
|
123.3
|
150.4
|
174.4
|
199.1
|
246.6
|
300.8
|
348.8
|
398.2
|
493.2
|
601.6
|
697.6
|
796.4
|
|
|
Control System
|
Dedicated heat pump controller,PID regulator,color touch screen
|
|||||||||||||||||
|
Energy Regulation
|
%
|
25——100
|
||||||||||||||||
|
Security
|
Overload, high voltage, wrong Phase, water, oil, antifreeze switch, high temperature protection
|
|||||||||||||||||
|
Compressor
|
Type
|
Imports of semi-closed screw compressors(Italy Refcomp, or Germany Bizter etc.)
|
||||||||||||||||
|
Quantity
|
set
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
2
|
2
|
2
|
2
|
4
|
4
|
4
|
4
|
||
|
Refrigerants
|
Refrigerant
|
Environmental protection Refrigerants R134a, R410a
|
||||||||||||||||
|
Charge
|
kg
|
100
|
120
|
155
|
215
|
265
|
310
|
360
|
430
|
525
|
620
|
720
|
858
|
1050
|
1240
|
1440
|
||
|
Evaporator
|
Type
|
High Efficient flooded type heat exchanger
|
||||||||||||||||
|
Water
|
Cooling
|
m3/h
|
50
|
60
|
77
|
107
|
132
|
155
|
180
|
215
|
262
|
310
|
360
|
429
|
525
|
620
|
720
|
|
|
Flow
|
Heating
|
m3/h
|
26
|
32
|
41
|
57
|
70
|
82
|
95
|
114
|
139
|
165
|
191
|
228
|
279
|
329
|
382
|
|
|
Pressure Loss
|
Kpa
|
≤80
|
≤90
|
|||||||||||||||
|
Interface Dim.
|
DN(mm)
|
100
|
125
|
125
|
125
|
150
|
150
|
150
|
150
|
150
|
200
|
200
|
125×2
|
200×2
|
200×2
|
200×2
|
||
|
Condenser
|
Type
|
Efficient shell and tube heat exchanger
|
||||||||||||||||
|
Water
|
Cooling
|
m3/h
|
26.3
|
32
|
41
|
57
|
70
|
82
|
95
|
114
|
139
|
165
|
191
|
228
|
279
|
329
|
720
|
|
|
Flow
|
Heating
|
m3/h
|
49.5
|
56
|
77
|
107
|
132
|
155
|
180
|
215
|
262
|
310
|
360
|
429
|
525
|
620
|
382
|
|
|
Pressure Loss
|
Kpa
|
≤80
|
≤90
|
|||||||||||||||
|
Interface Dim.
|
DN(mm)
|
100
|
125
|
125
|
125
|
150
|
150
|
150
|
150
|
150
|
200
|
200
|
125×2
|
200×2
|
200×2
|
200×2
|
||