Application range
CP01/PDU series socket power lightning protection device are applicable to the front side of various terminal consumer equipment of AC not more than 220V and rated current less than 10A providing protection against overvoltage arising from lightning to the power supply line and misoperation option from standard IEC61643 1 and GB50343
Main features
☆ High current capacity, low residual voltage
☆ Modularized design standard socket design convenient for installation and use
☆ Introducing multilayer protection technology strong protection ability high reliability.
☆ Build in temperature fuse safe and reliable.
☆ Red pilot lamp on indicate normal off indicate invalid
Main technical data
Type
CP01-6
PDU-6
Rated working voltage Un V
220
220
Max. continuous Voltage Uc V
320
320
Voltage protection level Up V
<1.3
<1.5
Rated working current Ie A
10A
Norminal discharge current In (8/20μs) kA
5
Max. Discharge current Imax (8/20μs) kA
10
Connection mode
Standard GB three-position socket
Response time
<25ns
Enclosure material
enhanced flame retardant nylon (flame retardancy:V0)
Response time
<100ns
Method of installation
35mm standard DIN rail installation
Cross-sectional area
≥2. 5 mm 2 stranded/ flexible
Installation instruction
1. The protector connected in parallel between the power channel and the protected device
2. Connect the input terminal to the power wire or insert the input terminal into the power socket, and then insert the power wire of protected device into socket make sure the reliable connection
3. Connect the earthing wire of the protector to the equalizing ring of the lightning protection system
4. If the red indicator light on after circuit be electrified. The lightning protection work is normal