LZA-POE
Application range
LZA-POE series are applied to network device powered by the CAT-5E,which is usually installed at the junction of LPZ1-LPZ3 of lightning protection zone, with function of two classes protection. These series can prevent the network device from damage caused by the overvoltage and overcurrent arising from lightning strike and industrial interference, so they are widely used in the wireless network bridge device.
Main features
☆ Modularization DIN rail design, convenient for installation and replacement.
☆ Build-in temperature control and circuit breaking technology, high security performance.
☆ Green light on in notice window indicates normal, indicates broken, clear and easily distinguished.
☆ Function of multilayer protection: power system and network signal system.
☆ Build-in 4mm2 elevating earthing terminal, more reliable earthing.
Main technical data
Items
|
|
|
Technical parameter
|
|
Rated working voltage Un V
|
|
1 4
|
Signal
interface
|
Max. continuous AC Voltage Uc V
|
|
3
|
Nominal start-up voltage V
|
wire-wire
|
≥3.6
|
|
wire-earth
|
90±20%
|
||
Norminal discharge current In (8/20μs) kA
|
2 5 .
|
||
Voltage protection level Up
(8/20 μs,2.5kA) V
|
wire-wire
|
≤15
|
|
wire-earth
|
≤300
|
||
Power
interface
|
Rated working voltage Un V
|
48
|
|
Max. continuous AC Voltage Uc V
|
60
|
||
Nominal start-up voltage (wire-wire,wire-earth) V
|
100V±10%
|
||
Norminal discharge current In (8/20μs) kA
|
5
|
||
Voltage protection level Up
(8/20 μs,5kA) V
|
wire-wire
|
≤150
|
|
wire-earth
|
≤300
|
||
Enclosure material and flame retardant resistance
|
enhanced flame-retarded nylon grade:V0
|
||
Terminal wiring ability
|
≥4 mm 2 stranded/flexible
|
Installment instruction
1.Series connection, connection at the input front side of protected device. 2.Connect the lightning earthing wire to the lightning grounding network in the computer room, make sure the earthing reliable and the earthing line less than 0.5m 3.Free mantenance, green light constant on indicate normal at 48V, off indicate broken, and then dismantle the protector and check the input power status. If the input power is normal, the protector is broken and need being replaced. If the signal is inaccessible, dismantle the product and check it again. If recover after dismantlement, the signal section is broken, the protector should be replaced immediately.