MRD-FD series generator neutral resistance box is dedicatedly applied to integrated equipment in power station where the generator neutral grounding through high resistance. The mian grade of voltage is from 6KV to 20KV, when one point of stator grounds it could limit grounding current at a very low level and effectively suppress arc grounding transient overvoltage.

Operating Environment
    1.Indoor application
     2.Environment temperature between -40℃ and +40℃
     3. Altitude does not excess 3000m
     4. Rlative humidity is not more than 95% (25℃)
     5.Power grid frequency: 58~62Hz(60Hz system), 48~52Hz(50Hz system)
     6.No corrosive gas or stem and no explosive dust on installation site.

Parameters of Grounding Transformer
Insulation Grade: H
Cooling-down Method: AN
Temperature Rise ≤ 100K
Proctective Grade of paper insulation dry-type connected transformer is IP00 (without casing), IP20 and ip23 (with casing)
Insulation level, impedance voltage, no-load loss and on-load loss are as per National Standards.
Test of inpedance: high voltage to low voltage or grouding ≥300 MΩ, low voltage to grounding ≥100 100 MΩ