MRD-FD generator neutral grounding resistors:

Parameters of Grounding Transformer
Insulation Grade: H
Cooling-down Method: AN
Temperature Rise ≤ 100K
Proctective Grade of paper insulation dry-type connected transformer is IP00 (without casing), IP20 and ip23 (with casing)
Insulation level, impedance voltage, no-load loss and on-load loss are as per National Standards.
Test of inpedance: high voltage to low voltage or grouding ≥300 MΩ, low voltage to grounding ≥100 100 MΩ
 
Generator Capacity
(MW)
100/125
200
300
600
900/1000
Generator Rating Voltage(kV)
10.5
13.8
15.75
18
20
20
24
24
27
Estimated Max. Capacitance Current of loop single phaseto ground(A)
4
5
6
8
10
Primary Side Voltage of ground Transformer(kV)
10.5/
13.8/
15.75/
18/
20/
20/
24/
24/
27/
Secondary Side Voltage of ground Transformer(kV)
0.22
0.22
0.22
0.22
0.22
Rated  Capacity of Ground Transformer (kVA)
30
30
50
50
63
Secondary Side Resistor Value(Ω)
1.0
0.8
0.5
0.4
0.3
Draw-out Voltage of Ground Protection
(kV)
0.1
0.1
0.1
0.1
0.1