MRD-FD generator neutral grounding resistors:
Parameters of Grounding Transformer
Parameters of Grounding Transformer
Insulation Grade: H
Cooling-down Method: AN
Temperature Rise ≤ 100K
Proctective Grade of paper insulation dry-type connected transformer is IP00 (without casing), IP20 and ip23 (with casing)
Insulation level, impedance voltage, no-load loss and on-load loss are as per National Standards.
Test of inpedance: high voltage to low voltage or grouding ≥300 MΩ, low voltage to grounding ≥100 100 MΩ
Generator Capacity
(MW)
|
100/125
|
200
|
300
|
600
|
900/1000
|
||||
Generator Rating Voltage(kV)
|
10.5
|
13.8
|
15.75
|
18
|
20
|
20
|
24
|
24
|
27
|
Estimated Max. Capacitance Current of loop single phaseto ground(A)
|
4
|
5
|
6
|
8
|
10
|
||||
Primary Side Voltage of ground Transformer(kV)
|
10.5/
|
13.8/
|
15.75/
|
18/
|
20/
|
20/
|
24/
|
24/
|
27/
|
Secondary Side Voltage of ground Transformer(kV)
|
0.22
|
0.22
|
0.22
|
0.22
|
0.22
|
||||
Rated Capacity of Ground Transformer (kVA)
|
30
|
30
|
50
|
50
|
63
|
||||
Secondary Side Resistor Value(Ω)
|
1.0
|
0.8
|
0.5
|
0.4
|
0.3
|
||||
Draw-out Voltage of Ground Protection
(kV)
|
0.1
|
0.1
|
0.1
|
0.1
|
0.1
|