GF302C Portable Three-Phase AC/DC Indicating Instrument Test Equipment
(Accuracy class 0.05/0.1)
It is suitable for power plant and substation work area of grid companies, make try department and the instrument classes, and
national levels measuring and testing institutions, railway, petroleum, chemical industry and other large industrial and mining
enterprises, scientific research units, etc.
This device is according to nation verification regulation JJG124-2005 "ammeter, voltmeter, power meter and resistance meter
calibration regulations and the relevant countries standard requirements and design three-phase 0.05 magnitude meter source
integration calibration device. The core technology of the function of device with digital signal processor (DSP) and 16 high-speed
digital converter composed of high precision work frequency communication terminal; The signal source of use is DSP and 16
high-speed digital-to-analog converters can control of the sine wave, distortion wave signal source; Equipment has high precision,
stable and reliable, and convenient operation, flexible, and other characteristics; Electric power system is used for electrical
measurement is the ideal equipment calibration.
1. I t can check all kinds of electric measurement of instrument including: AC/DC voltmeter, AC/DC ammeter, frequency meter,
phase meter, single three-phase AC active power meter, three-phase AC reactive power meter, synchronous meter, etc.;
2. Built-in electric measurement of verification procedure and indicating meter, automatic or semi-automatic for verification, saving
1000 group check data;
3. It is as a output voltage source, a current source and power source for high precision and high stability standard resource;
4. To use 6.4 inch big screen color display;
5. It is calibrated in the software, not need to open the case, stable and reliable;
6. Having short circuit, current output terminal, output voltage open protection and power amplifier overheating protection
function;
7. To have automatically failure detection function, shows fault part, the convenience users check line;
8. with RS232 interface, and computer connection for data management.
Electrical parameters | |
---|---|
Accuracy class | 0.05%, 0.1% |
Power supply |
Single phase AC 220V±10% or 110V±10%, 50/60 Hz or AC 110 V±10%, 50/60 Hz |
Communication Port | USB port |
AC voltage output | |
Range(U1,U2,U3) | 50 V, 100 V, 200 V, 400 V, 600 V |
Adjusting range | (0-120) % RG |
Adjust fineness | 0.005% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25 VA |
Output distortion degree | ≤0.3% (linear load) |
AC current output | |
Range(I1,I2,I3) | 0.5A, 1A, 2.5A, 5A, 10A, 20A |
Adjusting range | (0-120) % RG |
Adjust fineness | 0.005% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25 VA |
Output distortion degree | ≤0.3% (linear load) |
DC voltage output | |
Range | 75 V, 150 V, 300 V, 500 V, 1000 V |
Adjusting range | (0-120) % RG |
Adjust fineness | 0.005% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25 VA |
DC current output | |
Range | 0.5A, 1A, 2.5A, 5A, 10A, 20A |
Adjusting range | (0-120)% RG |
Adjust fineness | 0.005% RG |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Load capacity | 25 VA |
AC power output | |
Accuracy | 0.05% RG |
Stability | 0.01%/1min |
Frequency | |
Frequency range | 45-65 Hz |
Resolution | 0.001 Hz |
Accuracy | 0.002 Hz |
Power factor output | |
Adjusting range | -1 to 0 to +1 |
Adjust fineness | 0.0001 |
Accuracy | 0.0005 |
Phase angle | |
Scope | 0°-359.99° |
Resolution | 0.01° |
Accuracy | 0.05° |
Voltage/Current harmonic output | |
Times | 2nd-31th |
Content | 0-40% |
Phase | 0°-359.999° |
Configuration error | (10% RD + 0.1%), RD refers to the configuration value of harmonic contents |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 460x430x185 |
Weight (kg) | 18 |
Environmental conditions | |
Working temperature | 0°C to 40°C |
Storage conditions | -30°C to 60°C |
Relative humidity | ≤85% |