Specifications



Gas generator type: cummins brand 150 kw  Biomass Generator/Bio Gas Generator/Natural Gas Generator; 150 kw Biomass Generator/gas generator;150 kw Biomass Generator Gasification; 150 kw Biomass coal power/power plants;150 kw Coal power plants/biomass power plant; 150 kw Biomass Power/power ;

Conditions for Using
1. The temperature of the gas should not surpass 40ºC when the distance between the gas and the pressure regulating valve for air inflow is 1m.
2. The range of the pressure that this biogas generator set sustain should be 3kPa~10kPa and the fluctuated frequency should not surpass 1kPa/min.
3. The content of the methane in the biogas should not be lower than 45% and its fluctuated frequency should not surpass 2%/min.
4. The content of H2S should not surpass 200mg/Nm3 and the content of NH3 should not surpass 20mg/Nm3.

5. The granularity of the impurity should not surpass 5μ M and the content of the impurity should not surpass 30mg/Nm3.
6. The content of water in biogas used in this biogas generator set should not surpass 40g/Nm3.
7. For biogas with methane of about 30%~45%, low density biogas generator should be used.
For those gases which cannot reach the conditions above, this biogas generator set should be specially allocated after evaluation according to the specified composition, pressure, temperature, etc. Provided.