Product Main

Specifications

The residual current device (RCD) FIN is in conformity with the standard of VDE 0664, CEE27 and BS 4293.
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage. FIN ELCB is mainly suitable for varieties of plants and enterprises, buildings, construction, commerce, hotels and families. It can be used in circuits up to single-phase 240V; three phase 415V, 50 or 60 Hz.
Operating time (second)
I△n
2I△n
0.25A(or 5I△n)
 
0.2
0.1
0.04
 
Limited &#118alue of non-operating current for balance load or unbalance load
2In
 
In minimum &#118alue of rated making and breaking capacity
 
In=25
In=40
In=63
 
200
300
400
 
Rated conditional circuit current Inc(A)
1500
2000
3000
 
Endurance (times)
4000
 
         
 
 
SPECIFCATION
Type
FIN25
FIN40
FIN63
FIN100
Rated current In(A)
25
40
63
100
Rated operating current for earth leakage I△n(A)
0.03,0.1,0.3,0.5
0.1,0.3,0.5
Rated non-operating current for earth leakage I△n(A)
0.5I△n
Voltage Un(V)
240(220)V
415(380)V
Pole
2,4