Product Main

Quick Details

Brand Name: ZOANCO
Product name: conventional heat detector
Model Number: 105
Place of Origin: China (Mainland)
System Voltage (nominal: 24 VDC (9V~ 28VDC)
Standby Current: 40 uA @ 24VDC
Alarm Current: 30 mA @ 24VDC
Rate of Rise Detection: Responds to greater than 15F/min

Specifications

Skype firealarm87  /wechat 15220176087

Conventional Heat Detector
SPECIFICATIONS
Height:                             2.2? (55 mm) installed in Base
Diameter:                                4.0? (103 mm)
Weight:                            5.5 oz. (155 g)
Installation Temperatures:            14F to 122F (-10C to50C)
Operating Humidity Range:          10% to 93% Relative Humidity Non-condensing
Operating Voltage Range:               9 to 28VDC Volts Non-polarized
Standby Current:                    40A @ 24 VDC
Maximum Alarm Current (LED on: )   30mA @ 24 VDC
Fixed Temperature Rating:           135F (57C)

BEFORE INSTALLING
this detector must be installed in compliance with the control panel installation manual and meet the requirements of the authority having jurisdiction. In addition, the National Fire Protection Association has published codes, standards, and recommended practices for the installation and use of detectors, NFPA 72.
Therefore, the installer must be familiar with these requirements, with local codes, and any special requirements of the authority having jurisdiction..
NOTICE: this manual should be left with the owner/user of this equipment.
IMPORTANT: the detector must be tested and maintained regularly following NFPA 72 requirements. the detector should be cleaned at least once a year.
GENERAL DESCRIPTION
the device is intelligent sensors that utilize a state-of-the-art thermistor sensing circuit for fast response. these sensors are designed to provide open area protection with 50 foot spacing capability. The device is a rate-of-rise temperature sensor with 135F fixed temperature alarm.
the device is a rate-of-rise with fixed temperature alarm thermal detector utilizing a state-of-the-art dual thermistor sensing circuit. these detectors are designed to provide open area protection with 50-foot spacing capability, and are to be used with compatible control panels only.
Two LEDs on each detector light to provide 360 visibility of the detector indication.
INSTALLATION
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
NOTE: Verify that all detector bases are installed, that the initiating-device circuits have been tested, and that the wiring is correct.
 
Remove power from initiating-device circuits before installing detectors.
 
1. Wire the sensor base per the wiring diagram, Figure 1.
2. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
3. after all sensors have been installed, apply power to the control unit.
4. Test the sensor(s) as described in the TESTING section of this manual.
5. Notify the proper authorities that the system is in operation.