Brand Name: | zoanco |
---|---|
color: | red |
Executive standard: | ce |
Operating Voltage: | 90-270 VAC, 50 Hz, 2.3 amps |
Product name: | conventional fire alarm control panel |
Model Number: | ck1008 |
Place of Origin: | China (Mainland) |
AC Power: | 90-270 VAC, 50 Hz, 2.3 amps |
Maximum Charger Capacity: | 18 Amp Hour batter |
Maximum Charging Circuit: | Normal Flat Charge-27.6V @ 0.8 amp |
Normal Operating Voltage: | Nominal 24 VDC |
Alarm Current: | 15 mA threshold |
Maximum Loop Resistance: | 100 ohms |
Quick Details
Specifications
Skype firealarm87 /wechat 15220176087
Conventional Fire Alarm Control Panel with eight Zones
Conventional Fire Alarm Control Panel with eight Zones
Key Specifications/Special Features
Eight Style B (Class B) Initiating Device Circuits (IDCs).
All zones accept two-wire smoke detectors and any normally-open contact devices.
Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
Alarm, Trouble and Supervisory, Form-C relays standard.
24-volt operation.
Resettable four-wire smoke detector power @ 500 mA.
Non-resettable power @ 500 mA.
One-man walk-test programmable for silent or audible test.
Disable/Enable control per IDC.
Reverse polarity protection.
the CK1000 is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. the panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level.
this series of panels are basically the same in application and operation, their differences are shown in Table 1-1. CK1000 will be described as the example in the following sections.
Table 1-1
FACP |
Number of Detection Zones |
Number of Sounder Outputs |
Output Delay Settings |
CK1004 |
4 |
1 |
N/A |
CK1008 |
8 |
2 |
N/A |
CK1016 |
16 |
4 |
N/A |
1.1 Product Features
L 4,8,16 Class B Initiating Device Circuits (IDCs)
? All zones accept conventional detectors and any normally open contact device
L Four Class B Notification Appliance Circuits (NACs)
L One Form-A Alarm Relay
L One Form-A Trouble Relay
L One Form-A Supervisory Relay
L 3.0 amps of system power
L Max 20 conventional detectors in one zone.
L Auto/Manual mode setting enable walk test.
L Each Zone can be disabled,
L Sound output can be disabled.
L Manual active sound output enabled.
L Able to report short and broken circuit of detection zones.
L Designed with standby batteries and space provision for two sealed lead-acid batteries.
L Testing and disable functions.