Standard: 
GB/T 10228-1997 GB/T10088-2004 GB4208-1993 
Rated high-voltage: 10(11, 10.5, 6.6, 6.3)KV Rated low-voltage: 0.4KV 
Connection group: Dyn11 or Dyn0 Tapping rang of high-voltage: +-5% or +-2*2.5% 
Insulating level: LI75AC35/LI 0AC5 Frequency: 50Hz
Rated capacity(kVA)    Voltage group(kV) Connection method loss(kW) No-load current (%) Impedance voltage (%) Insulating level Weight(Kg)
No- load Load (120° C)
10 High-voltage 11 /10.5 /10 /6.3 /6 
Low-voltage 0.4
Yyno / Dyn11 0.150 0.325 4.5 4 F/F 130
20 0.185 0.630 4.0 170
30 0.215 0.750 3.2 330
50 0.305 1.055 2.8 380
63 0.370 1.280 2.7 440
80 0.415 1.460 2.6 510
100 0.450 1.665 2.4 590
125 0.530 1.955 2.2 650
160 0.610 2.250 2.2 780
200 0.700 2.675 2.0 930
250 0.810 2.920 2.0 1040
315 0.990 3.670 1.8 1180
400 1.100 4.220 1.8 1450
500 1.305 5.170 1.8 1630
630 1.510 6.220 1.6 1900
630 1.460 6.310 1.6 6 1900
800 1.710 7.360 1.6 2290
1000 1.990 8.600 1.4 2700
1250 2.350 10.260 1.4 3130
1600 2.755 12.420 1.4 3740
2000 3.735 15.300 1.2 4150
2500 4.500 18.180 1.2 4810
3150 5.780 23.700 1.0 8 5800
4000 6.700 28.500 1.0 7100
More Product Features
Standard:  GB/T10228-1997, GB6450-1986
Unit Price:  Negotiable
Shipment Terms:  FOB
Payment Terms:  T/T
Phase:  Three
Type:  Transformer
Export Markets:  South America, Eastern Europe, Southeast Asia, Africa, Mid East, Eastern Asia, Western Europe