Product Main

Specifications

Copper Conductor PVC insulated Building Wire
 
1. The applications: Rated voltage (U0/U) 0.6/1KV in transmission & transformation line & for water-proofing purpose .
2. Standards: IEC60502-1 2004  ISO9001:2008
3. Product Features:
1) No necessary to heat up in advance while installing above 0oC.
2) Max. continuous normal operating Temperature: 70oC (PVC Sheathed Cable).
3) Max. Permissible temperature at short circuit (5s. at longest): 160oC.
4) Permissible bending radius:
Single core: ≥20(d+D)±5%.
Three-core:≥15(d+D)±5%(D is the actual overall diameter of cable, and d is the actual overall diameter of conductor).
5)Structrue
Nominal
sectional area
mm2
Conductor
No/Dia.
mm
Nominal
Insulated thick
mm
Max overall
Dia.
mm
Condcutor
Resistance at
20
Min insulated
resistance at
70MΩ/km
Weight
Kg/km
Cu Al Cu Al
1.5 1/1.38 0.7 3.3 12.1 - 0.011 19.2 -
1.5 7/0.52 0.7 3.5 12.1 - 0.010 20.6 -
2.5 1/1.78 0.8 3.9 7.41 11.8 0.010 30.8 15.0
4 1/2.25 0.8 4.4 4.61 7.39 0.0085 45.5 21.0
6 1/2.76 0.8 4.9 3.08 4.91 0.0070 65.0 29.0
10 7/1.35 1.0 7.0 1.83 3.08 0.0065 110.0 52.0
16 7/1.70 1.0 8.0 1.15 1.91 0.0050 170.0 70.0
25 7/2.14 1.2 10.0 0.727 1.20 0.0050 270.0 110.0
35 7/2.52 1.2 11.5 0.524 0.868 0.0040 364.0 150.0
50 19/1.78 1.4 13.0 0.387 0.641 0.0045 500.0 200.0
70 19/2.14 1.4 15.0 0.268 0.443 0.0035 688.0 269.0
95 19/2.52 1.6 17.5 0.193 0.320 0.0035 953.0 360.0
120 37/2.03 1.6 19.0 0.153 0.253 0.0032 1168.0 449.0
150 37/2.25 1.8 21.0 0.124 0.206 0.0032 1466.0 551.0
185 37/2.52 2.0 32.5 0.099 0.164 0.0032 1808.0 668.0
 
Our company can produce both flame retardant and non-flame retardant series of PVC power cables. Our products can be produced according to our works specifications which are equivalent to GB12706, IEC60502, IEC60332, IEC60754, and its some indexes are superior to standards as stated above..
The flame-retardant cable covers all kinds of low-smoke, free-halogen, low-smoke halogen free and three classes of A, B, C. We can design and manufacture special PVC cables according to the other standards require by the customers, such as heavy section cut part conductors, water-resistant, defend termites, defend mouse, and so on.