PITE 5303C-22 Three Phase standard reference meter, developed by PITE, is a standard electric energy meter with characteristics of wide-range, multifunction and high-precision.
PITE 5303C-22 Three Phase Standard Meter
PITE 5303C-22 Three Phase standard reference meter, developed by PITE, is a standard electric energy meter with characteristics of wide-range, multifunction and high-precision. It has different option of accuracy class of 0.02, 0.05 and 0.1. By adopting techniques of DSP, embedded system and automatic temperature balancing and other compensation, it has not only advantages of light weight, small size, high precision, high performance, powerful function, original interface, ease-to-use, but also work stability.
The product can be widely used in fields of electric energy measuring, electric energy laboratories and other relevant industry, not only in laboratories but also at the industrial field.
Technical indicators
1. Input
1.1 Voltage Input
Input Range (V): 40—480
Input measurement (V): 60, 120, 240, 480
Overload Capability (V): 600
Input load: ≤0.5mA (480V)
1.2 Current Input
Input Range (A): 0.01—100
Input measurement (A): 100, 50, 25, 10, 5, 2.5, 1, 0.5, 0.25, 0.1, 0.05, 0.025
Overload (A): 150
Input load ≤0.3mΩ (100A—2A)
≤0.4Ω (1A—0.01A)
2. Output
2.1 Output Pulse Frequency
fH=CH.p/3600 (Hz)
fL=fH/10000 (Hz)
2.2 Output electrical level: TTL
2.3 Pulse Constant
High Frequency Pulse Constant CH (P/kwh)
|
100A
|
50A
|
25A
|
10A
|
5A
|
2.5A
|
480V
|
4×105
|
8×105
|
1.6×106
|
4×106
|
8×106
|
1.6×107
|
240V
|
8×105
|
1.6×106
|
3.2×106
|
8×106
|
1.6×107
|
3.2×107
|
120V
|
1.6×106
|
3.2×106
|
6.4×106
|
1.6×107
|
3.2×107
|
6.4×107
|
60V
|
3.2×106
|
6.4×106
|
1.28×107
|
3.2×107
|
6.4×107
|
1.28×108
|
|
1A
|
0.5A
|
0.25A
|
0.1A
|
0.05A
|
0.025A
|
480V
|
4×107
|
8×107
|
1.6×108
|
4×108
|
8×108
|
1.6×109
|
240V
|
8×107
|
1.6×108
|
3.2×108
|
8×108
|
1.6×109
|
3.2×109
|
120V
|
1.6×108
|
3.2×108
|
6.4×108
|
1.6×109
|
3.2×109
|
6.4×109
|
60V
|
3.2×108
|
6.4×108
|
1.28×109
|
3.2×109
|
6.4×109
|
1.28×1010
|
*Low Frequency Pulse Constant CL=CH/10000
3. Accuracy
3.1 Accuracy Class: 0.02, 0.05, 0.1
3.2 Power Measurement Accuracy
Active Power: 0.02%, 0.05%, 0.1% (PF≥0.5)
Reactive Power: 0.05%, 0.1%, 0.2% (PF≥0.5)
3.3 Energy Measurement Accuracy
Active Energy: 0.02%, 0.05%, 0.1% (PF≥0.5)
Reactive Energy: 0.05%, 0.1%, 0.2% (PF≥0.5)
Reactive Energy: 0.05%, 0.1%, 0.2% (PF≥0.5)
4. Display
4.1 Display Content
Three-phase voltage U1, U2, U3 (V
Three-phase voltage U1, U2, U3 (V
Three phase four wire U1, U2, U3 for Uan, Ubn, Ucn
Three phase three wire U1, U2, U3 for Uab, Ubc, Uca
Three phase current Ia, Ib, Ic (A)
Active Power: P (W)
Apparent Power: S (VA)
Reactive Power: Q (VA)
Power Factor: Pf -1.0000—1.0000
Phase Angle: θ (0o-360o)
Input Signal Frequency: F (Hz)
4.2 Display Digits: 5 digits
5. Power Supply: 220V±10%, 50Hz±5%,
Power Consumption: about 20VA.
Power Consumption: about 20VA.
6. Preheat Time: 30 minutes
7. Working Environment
Temperature: 5℃—40℃
Relative Humidity: ≤85%
Non-corrosive gases
8. Dimensions: 482mm×480mm×140mm
9. Gross weight: 9kg