Product Main

Specifications

1.1General introduction
GDGS different frequency automatic dielectric loss tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ,and capacitance of all kinds of high voltage electrical equipments’ on the spot of power plants, substations etc.
 
1.2Technical Index
1.
Condition of Use
-5°C~40°C, RH<80%
2.
Power Source
AC 110V±10%  Without Frequency Limit
3.
High Voltage Output
 
 
 
Range
1KV~10KV, every 1KV
 
Precision
5%
 
Maximum Current
140mA
 
Capacity
1000VA
4.
Self-Excited Power
 
 
 
Voltage Range
AC  0V~30V
 
Frequency
45Hz /55Hz
 
Maximum Current
15A
5.
Definition
tgδ: 0.001% , Cx: 0.1PF
6.
Precision:
 
 
 
 
7.
Measuring Range
tgδ Without Limit
 
 
 
 
10kV
 
1kV
 
 
CVT Test
 
8.
Size
470mm(L) ×320mm(W)×390mm(H)
 
Weight
30kg