Product Main

Quick Details

Phase: Single Phase
Display Type: Digital Only
Model Number: GF112
Brand Name: GFUVE
Place of Origin: China (Mainland)
GF112: portable single phase standard meter
Accuracy class: 0.5%/0.3%/0.2%

Specifications

GF112 Portable Single Phase Standard Meter

(Accuracy class 0.5%/0.3%/0.2%)

 
 
Product Description

GF112 portable single phase standard meter with human oriented design , small configuration and lightweight. Suit for electric power departments,  measuring and quality examining departments and electric lab to field use.

Features
  • External power supply or test lead power, suit for fieldwork
  • With 2pcs clamp CT to test ratio of current transformer. (Optional) 
  • Large size display screen, direct viewing and convenient 
  • Internal communication port for PC control
  • Multi power supply ways for different testing occasion
  • Large capacity storage device for mass memory

Technical Data

 
Test Voltage
Range
10-420V
Error
±0.3%
Harmonic
2nd -- 31st
Test Current
Range (clamp CT)
40A
5A,20A,40A,100A (option)
Error (clamp CT)
±0.3% (5A, 100A)
Harmonic
2nd -- 31st
Power measure error
Active power (clamp CT)
±0.3% (5A, 100A)
Reactive power (clamp CT)
±0.5%
Energy measure error
Active energy (clamp CT)
±0.3% (5A, 100A)
Reactive energy (clamp CT)
±0.5%
Phase angle
Range
0o – 360o
Error
±0.1o
Frequency
Range
45Hz – 65Hz
Pulse output
Low frequency output(CL)
800imp/kWh
Pulse ratio
1:1
Output level
5V
Pulse input
Input channel
1
Input level
5 -- 10V
Input frequency
Max. 100Hz
Display
Resolution
2.8" LCD (320×240)
Function
Waveform
Energy accumulation
CT ratio test
Local parameter input
Recorder check
Data storage
Data storage qty
1000
Communication port
RS232
Communication with PC
Upload data
Other
Voltage Supply way
External power
 test lead power
Voltage Supply
110-270V, 50/60Hz
Ambient temperature
-25°C -- +45°C
Relative humidity
20% -- 95%
Dimensions (W×H×D) (mm)
185×67×30
Weight (kg)
0.5kg