Product Main

Quick Details

Model Number: GF312B
Brand Name: GFUVE
Place of Origin: China (Mainland)
GF312B: Portable three phase energy meter calibrator with printer
Accuracy class: 0.05%,0.1%

Specifications

GF312B Portable Three-Phase Energy Meter On-Site Calibrator

(Accuracy class 0.05%/0.1%/0.2%)
 
 
Product Description
 

GF312B portable three-phase kWh Meter Calibrator is used to calibrate three phase, single phase, active or reactive energy meter under work, and also it can be used as voltage, current and power meter to measure AC parameter of three phase power line, also it can measure wave distortion factor and 2 to 63 time harmonic wave .

 
Features and Functions
 

Three phase active or reactive electricity energy meter;

Calibrate three phase, single phase, active or reactive meter error;

Measure U(voltage) of three phase or single phase;

Measure I(current) of three phase or single phase;

Measure active power of three phase or single phase;

Measure reactive power of three phase or single phase;

Measure apparent power of three phase or single phase;

Measure power factor of three phase or single phase;

Measure phase angle between voltage and current;

Measure frequency of power line;

Display vector diagram;

Display waveform of U and I;

Analyze and display content of harmonic of U and I;

Store and look measured data;

Optional 5 A, 20 A, 100 A, 500 A, 1000 A, 2000 A current clamp;

Measure CT variable ratio;

Print the data of measurement on site;

 
 
Specification
 
Test Voltage
Range
6V – 600V
Error
±0.05% (30V – 600V)
±0.1% (5V – 30V)
Harmonic
2nd -- 63st
Test Current
Range (direct connection)
20mA – 20A
Error (direct connection)
±0.05% (100mA – 20A)
±0.1% (20mA – 100mA)
Harmonic
2nd -- 63st
Power measure error
Active power (direct connection)
±0.05% (0.1A – 20A)
±0.1% (0.02A – 0.1A)
Reactive power (direct connection)
±0.1% (0.1A – 20A)
Energy measure error
Active energy (direct connection)
±0.05% (0.1A – 20A)
±0.1% (0.02A – 0.1A)
Reactive energy (direct connection)
±0.1% (0.1A – 20A)
Phase angle
Range
0o – 360o
Error
±0.05o
Frequency
Range
45Hz – 65Hz
Pulse output
High frequency output(CH)
1×1011 (1mA – 10mA)
1×1010 (10mA – 0.1A)
1×109 (0.1A – 1.0A)
1×108 (1.0A – 10A)
1×107 (10A – 120A)
Low frequency output(CL)
2×10-5×CH
Pulse ratio
1:1
Output level
5V
Pulse input
Input channel
1
Input level
5 – 24V
Input frequency
Max. 2MHz
Display
Resolution
6" TFT (640×480)
Function
Vector diagram
Waveform
Energy accumulation
Communication port
RS232
Communication with PC
Other
Voltage Supply way
External power
Voltage Supply
220V ± 10%, 50/60Hz ± 2Hz
Ambient temperature
-10°C -- 40°C
Relative humidity
30% -- 80%
Dimensions (W×H×D) (mm)
390×200×160
Weight (kg)
3kg