Main Features
  Double conversion PWM (pulse width modulation) inverter technology and with output isolated transformer built-in
  Peak current protection, easily supply linearload and strongly resist cold load impact.
  Output short circuit protection and generator compatible.
  DC starts function.
  N+1 or N+X parallel redundancy system.
  Independent large current charger.
  User friendly LCD/LED display, network monitoring management system. 

Specification
   
 
Model JY300L31 JY400L31
Capacity VA/Watts 30KVA/24KW 40KVA/32KW
Input Phase 3×380Vac+N+W (3-phase)
Voltage 320~480Vac
Frequency 50Hz±5%
Output Voltage 220/230/240Vac±1% ( static load )220/230/240Vac±2% (50~0% load change)
Frequency 50Hz±0.1%(On battery)
Waveform Pure sine wave
Distortion <1%(with full linear load)<3%(with full nonlinear load)
Efficiency AC/AC >85%
Switching time 0ms
Output power factor 0.8
DC start Yes
Manual bypass Yes
Parallenl redundant Yes
Parallel circulation <3%
Battery Type Maintenance-free, sealed lead-acid
Numbers 30pcs 30pcs
Voltage 360Vdc 360Vdc
Charge current 10-20A (adjustable)10-20A (adjustable)
Protection Overload >120% for 10 minutes&bypass or shutdown;
>150% for 60 seconds&bypass or shutdown;
Short circuit Circuit protection,bypass switch trip
Noise suppressor EM I / RFI filter
Low battery Shut down
Output abnormal Inverter auto shut down
Crest ratio 3:1
Generator compatible Yes
Display LED UPS operating status, battery status, UPS fault, Load
LCD Input/output voltage/frequency,battery voltage,output power,mains/load abnormal records
Alarm Alarm Mains failure,low battery,overload, UPS fault
Mute Automatic
Noise At 1 meter <50dB
Physical Dimension(W×D×H) 430×985×1030 430×985×1030
Weight ( kg) 280 345
Enviroment Temperature 0~40℃
Humidity <95% (non condensing)
Interface Port RS232/dry contact/RS422/RS485/SNMP slot(optional)
Function IEC62040