Product Main

Specifications

Main Features
  The latest DSP design make protection more speedy, ensure UPS more reliable
  High frequency technology provide a broad development space for UPS power
  Complete protection and high availability meet the needs of a wide range of facility
 
◇ Wide input range, advanced power factor correction, input power factor reach 0.99;
◇ Output short circuit protection by using all digital technology;
◇ Bypass-Inverter conversion condition control;
◇ Sensitive peak current detection and protection to make UPS can supply nonlinear load high ability in resisting cold load impact;
◇ Advanced transformer less design and unique Energy Saving Inverter Switching to make UPS efficiency up to 90%;
◇ Unique low ripple charger prevent battery charing from overheating, prolong the battery life;
◇ Input / output anti-interfereence design, conducted interference & radiation conform to safety standard;
◇ Frequency auto sensing from 45-65Hz;
◇ Compatible with various generators, greatly reduce the running cost.
◇ Redundancy operation, further improve system reliability.
  Monitoring and Network Management
  LED and LCD double display UPS operating status. RS232 and SNMP slot make it possible to realize multi-functional,multi purpose monitoring and network communications.
  Specification
   
 
Model  
Capacity VA/Watts: BH100L31/8KW,BH150L31/12KW,
BH200L31/16KW (w/o battery, long time running type)
Rectifier  
Phase: 3 phase in 1 phase out
Voltage range: 304 ~ 478 Vac
Frequency: 45Hz~65Hz ( Auto tracking)
Power Factor: ≥0.98
Inverter features
Voltage range: 220Vac±1%
Frequency: Mains: 46Hz input frequency 54Hz,auto Tracking;
Input below 46Hz or above 54Hz,lock output frequency at 50Hz
Battery: 50Hz±0.2%
Waveform: Pure sine wave
Distortion THD<3% with nonlinear load; THD<1% with linear load
Power factor: ≥0.8
Over load: >125% for 10 mins, then transfer to bypass or shutdown
>150% for half cycle, then transfer to bypass or shutdown
Crest ratio: 3∶1
General features
Efficiency: >90%(AC to AC)
Switching time: 0ms
Noise suppressor: < 50dB (At 1 meter)
Working temperature: 0- 40℃
Environment Humidity: < 95% non-condensing
Safety standard: GB/T14715, EN50091-1/2
Parallel redundancy: Yes
DC starts: Yes
Generator compatible: Yes
Display: LED UPS operating status, inverter/bypass status,battery,load
LED UPS operating status, inverter/bypass status,battery,load
Alarm: Mains fault,battery low,overload,short circuit,UPS fault
Mute: Manual
Battery features
Type: Maintenance-free sealed lead-acid
DC Voltage: 192Vdc or 240Vdc
Noise suppressor: EMI/RFI filter
Low voltage on battery: Shut down
Output abnormal: Inverter auto lock
Communication Interface
connect: True RS-232 communication port; SNMP(option)
Function: Status of mains and battery, mains failure, battery voltage, remote shut down,
menu operation
Physical parameter
Dimension(W×D×H mm) 10KVA/15/20KVA: 260X517X606( w/o battery, long time running type)
Weight (Kg): BH100L31/27,BH150L31/34; BH20L31l/35