Applications :
- These cables are flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.
Standards :
-
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction :
- Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
- Conductor Screen : Semi conducting material.
- Insulation : Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
- Insulation Screen : Semi conducting material and tinned copper wire braid.
- Bedding : Halogen free compound.
- Armour : Tinned copper wire braid.
- Outer Sheath : Halogen free thermosetting compound, SHF2 (for TYPE P2), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P2/P9),coloured red.
Dimensions and Weight :
Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm |
Nominal Sheath Thickness mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|
Inner | Outer | ||||
1×16 | 2.5 | 1.4 | 1.1 | 22.8 | 780 |
1×25 | 2.5 | 1.5 | 1.1 | 24.0 | 1020 |
1×35 | 2.5 | 1.5 | 1.2 | 25.1 | 1155 |
1×50 | 2.5 | 1.6 | 1.2 | 26.3 | 1320 |
1×70 | 2.5 | 1.6 | 1.3 | 28.2 | 1595 |
1×95 | 2.5 | 1.7 | 1.3 | 30.0 | 1905 |
1×120 | 2.5 | 1.8 | 1.4 | 31.8 | 2235 |
1×150 | 2.5 | 1.8 | 1.4 | 33.5 | 2550 |
1×185 | 2.5 | 1.9 | 1.5 | 35.4 | 3015 |
1×240 | 2.6 | 2.0 | 1.5 | 38.8 | 3725 |
1×300 | 2.8 | 2.1 | 1.6 | 42.3 | 4625 |
1×400 | 3.0 | 2.2 | 1.7 | 46.6 | 5420 |
1×500 | 3.2 | 2.4 | 1.8 | 50.8 | 6610 |
1×630 | 3.2 | 2.5 | 1.9 | 55.1 | 8170 |
3×16 | 2.5 | 2.2 | 1.6 | 44.9 | 2930 |
3×25 | 2.5 | 2.3 | 1.7 | 45.4 | 3390 |
3×35 | 2.5 | 2.4 | 1.8 | 47.6 | 3820 |
3×50 | 2.5 | 2.5 | 1.9 | 50.9 | 4495 |
3×70 | 2.5 | 2.7 | 2.0 | 54.8 | 5585 |
3×95 | 2.5 | 2.8 | 2.1 | 58.9 | 6765 |
3×120 | 2.5 | 3.0 | 2.2 | 63.5 | 8165 |
3×150 | 2.5 | 3.1 | 2.3 | 67.4 | 9495 |
3×185 | 2.5 | 3.3 | 2.4 | 75.8 | 10660 |
3×240 | 2.6 | 3.5 | 2.5 | 82.3 | 11660 |
3×300 | 2.8 | 3.8 | 2.7 | 89.3 | 12940 |