Product Main

Specifications

Applications :
  • These cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.
Standards :
  • IEC 60092-354 IEC 60092-351
    IEC 60092-359 IEC 60332-1
    IEC 60331-21 IEC 60332-3-22
    IEC 60754-1,2 IEC 61034-1,2
    NEK 606:2004  

Construction :
  • Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
  • Conductor Screen : Semi conducting material.
  • Insulation : Halogen-free EPR. XLPE can be offered as an option.
  • Insulation Screen : Semi conducting material and tinned copper wire braid.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath1 : Halogen free thermosetting compound, SHF2, coloured red.
  • HC-fire protection : Extruded thermoplastic fire protection compound.
  • Taping : Lapped glass fibre tape.
  • Outer Sheath2 : Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.

Dimensions and Weight :
 
Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Diameter Over Bedding
mm
Nominal Diameter Over Sheath1
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
1×70 3.4 23.5 30.0 62.0 5220
1×95 3.4 25.5 32.0 64.5 5900
1×120 3.4 27.5 34.0 66.5 6340
1×150 3.4 28.5 35.0 67.5 6670
1×185 3.4 30.5 36.5 69.0 7320
1×240 3.4 33.0 39.0 72.0 8250
1×300 3.4 35.0 41.5 74.5 9280
3×50 3.4 47.0 55.0 89.0 10970
3×95 3.4 54.0 62.5 97.0 14230
3×150 3.4 60.0 70.5 106.0 17400