Product Main

Specifications

WM 400 SERIES AC Voltage Measurement
DESCRIPTION (AVERAGE RMS AND TRUE RMS Responding)
WM400 Series AC voltage transducers and transmitters are designed to provide a DC output proportional to the AC voltage input. It features with high accuracy, low wiring costs, easier installation and low power consumption and low cost. These

APPLICATIONS (For General Applications)
Building Automation, Energy Management
Monitor motor faults
Monitor lighting elements
Monitor heating elements
WM 400 series AC Voltage transducers have meet requirement of IEC 61010-1
TECHNICAL DATASHEETS
Input Signal (AC VOLATEG)
Ranges available up to and including 1000V AC
Allowed overload
2 times of input voltage value, continues for 1 second; stop 10 seconds, then repeat 10 times.
Linear range
0%-120%
Frequency range
50Hz; 60Hz;
Aperture case style
S type
U type
Input impedance
Ri=Ux*1kΩ/V
Output signal
DC voltage, DC current
True RMS sensing output
Output specifications
DC 0-5V;DC 0-10V;
DC 0-20Ma; DC 4-20Ma;
Accuracy
0.2% or
0.5%
Load capacity
For voltage output:5mA
For current output: 6V
Response Time
300ms
Thermal drift
150ppm to 300ppm ( depending on output value)
Other characteristics
 
Power supply
Available in
Other output:DC12V;DC24V
           AC/DC 85V-265V
Static current
5mA to 24mA (depend on the output)
Working temperature
0~50℃
Storage temperature
-25 ℃ ~70℃
Isolation
Total galvanic isolation circuitry design
Two wire system (loop powered) input to output isolated
Also available in: input to output to power supply isolated
Isolation voltage
2500VDC-3500VDC
Case protection
IP 20
Mean Time Between Failure
50000 hours
Case material
According to UL94V-0; Fire Retarded
Installation
Rail mounting According European standard EN50022. or M3 screw
Dimensions
Length*width*height
for U case style: 105mm*23mm*70.5mm
for S case style:105mm*24mm*66
 
MODEL SELECTION TABLE
AC voltage  (Average RMS Responding)
For Isolation: (1) 2: means input to output isolated, power supply connects output terminal;
            ) 3 : means input to output to power supply isolated;
Model
Input (ac)
Output
Power supply
Aperture
Isolation
Price
For ac voltage output
 
WMV411D07
Miniature type
10V…1000V(need to add external current limit resistor according to 1KΩ/V ratio)
 
AC 0-3.5V
AC 0-5V
DC±12V
DC±15V
-
2 ISOLATION
 
WMV121G07
50Mv…50V
Add external resistor for extended measurement to 1000 V);
AC 0-3.5V
AC 0-5V
DC±12V
DC±15V
-
2 ISOLATION
 
WMV121G27
75Mv;100Mv;
AC 0-3.5V
 
DC±12V
 
 
2 ISOLATION
 
For dc current output
WMV414U01
10V… 1000V;
0-20 mA;
4-20 mA
DC +12V;24V
-
2 ISOLATION
 
WMV414U05
10V…1000V;
0-20 mA;
4-20 mA
DC +24V
-
3 (Triple Isolation)
 
WMV414U09
10V…1000V;
0-20 mA;
4-20 mA
AC/DC 85V-265V
-
3 (Triple Isolation)
 
For dc 4-20Ma output (2-wire loop powered)-
 
WMI414U03
10V…1000V;
DC 4-20mA
DC +12V;24V
-
Loop powered
 
For dc voltage output
WMV412U01
10V…1000V;
0-5V;0-10V
DC +12V;24V
-
2 ISOLATION
 
WMV412U05
10V…1000V;
0-5V;0-10V
DC +24V;
-
3 (Triple Isolation)
 
WMV412U09
10V…1000V;
0-5V;0-10V
AC/DC 85V-265V
-
3 (Triple Isolation)
 
WMV412D01
Miniature type
10V…1000V(need to add external current limit resistor according to 1KΩ/V ratio)
DC 0-5V;
DC +12V;15V;
-
2 ISOLATION
 
For TRUE-RMS sensing
The series are designed for applications where AC voltage waveforms are not purely sinusoidal. More precise and accurate than other devices, these units are ideal in chopped wave and phase fired control systems.
 
WMV415S01
10V…500V;
0-5V;0-10V
DC +12V;24V
-
2 ISOLATION
 
WMV415U01
10V…1000V;
0-5V;0-10V
DC +12V;24V
-
2 ISOLATION
 
WMV417S01
10V…500V;
0-20 mA;
4-20 mA
DC +12V;24V
-
2 ISOLATION
 
WMV417U01
10V…1000V;
0-20 mA;
4-20 mA
DC +12V;24V
-
2 ISOLATION